background image

4.3.7.2  Setpoints & On/Off Control

Auto Setpoint Deviation:

If “enabled”, allows changes to Setpoint 1 to be

made automatically to Setpoint 2. This mode is very helpful if the Temperature

changes often. 

In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts

away from SP1--this relation remains fixed when SP1 is changed. 

For instance: Setting SP1=200 and SP2=20 and enabling SP Deviation means

that the absolute value of SP2=220. 

Moving SP1 to 300, the absolute value of SP2 becomes 320.

Setpoint 1: 

This setpoint controls Alarm 1

Setpoint 2: 

This setpoint controls Alarm 2

Permanent Store:

Check to save Setpoints in the Meter’s permanent storage.

On/Off 1 and On/Off 2:  

To enable and disable On/Off Control.  Enabling On/Off

Controls will disable the Alarms, and vice versa.

DeadBand: 

The Dead Band or neutral zone, is the number of degrees counts

around Setpoint 1(or Setpoint 2 if On/Off 2) which the temperature value must

pass above or below the Setpoint before the output changes state.

Action:  

The error that results from the measurement of the Process Variable

may be positive or negative since it may be greater or smaller than the Setpoint.

If a positive error should cause the Meter output to increase (i.e. cooling), it

would be called 

Direct Acting

.  If a negative error should cause the output to

increase (i.e. heating), it would be called 

Reverse Acting

.

40

Summary of Contents for wi Series

Page 1: ...inute 1 Day 1 Week 1 Month 1 Year 0 5 C Div 50 1200 300 100 0 10 Div 90 hPa Div C hPa Tue Feb 5 10 19 10 PDT 2008 Tue Feb 5 10 18 10 PDT 2008 http 192 168 1 200 Min Max Temperature 48 0 41 0 P1 Proces...

Page 2: ...is document is believed to be correct but OMEGA Engineering Inc accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING These products are...

Page 3: ...10Base T RJ45 Pinout 16 2 2 2 10Base T Crossover Wiring 16 Part 3 Network Configuration 17 3 1 Ethernet MAC Address 17 3 2 Network Protocols 17 3 3 DHCP 17 3 4 DNS 18 3 5 IP Address 19 3 5 1 Default...

Page 4: ...e 65 4 8 1 Installation 65 4 8 2 Program Options Setup and Configuration 66 4 8 3 Device Settings and Configuration 67 Part 5 Environment operating Conditions 69 5 1 General Deployment Guidelines 69 5...

Page 5: ...cessing the Wireless System for Configuration 23 Figure 4 4 Access Control 24 Figure 4 5 Wireless System Home Page Menu 25 Figure 4 6 LOGIN and ADMINISTRATOR passwords 26 Figure 4 7 Readings 27 Figure...

Page 6: ...Mail Notifier Profile Setup 66 Figure 4 31 Mail Notifier Device Settings 68 Figure 5 1 Operation in Buildings 70 Figure 5 2 Fresnel Zone 71 Figure 5 3 Materials in Buildings 72 LIST OF TABLES Table 2...

Page 7: ...he switch shall not be incorporated in the main supply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment an overcurre...

Page 8: ...ssistance please call the nearest Customer Service Department listed in this manual Manuals Software The latest Operation Manual as well as free configuration software iConnect are available from the...

Page 9: ...ries system let s you monitor and record temperature over an Ethernet network or the Internet without any special software just your Web Browser ETHERNET The wiSeries meter controller scanner is an in...

Page 10: ...reset by the operator The meter can also be programmed to display only one unchanging color GREEN AMBER or RED This is a useful way to let an operator identify at a glance temperature values in three...

Page 11: ...erature Changes display to Configuration Mode and advances through menu items Make sure to press twice Stand by followed by pressing stop communication before entering the Configuration mode Used in C...

Page 12: ...thernet board ACTIVITY LED Red Blinking Indicates network activities receiving or sending packets NET LINK LED Green Solid Indicates good network link TX LED Yellow Blinking Indicates transmitting dat...

Page 13: ...2 1 3 Dimensions Figure 2 3 Mounting Dimensions 3 780 96 00 1 890 48 00 0 700 17 78 4 325 109 85 1 2 C F 1 2 RH D 1 2 C F PANEL THICKNESS 0 25 6 4 MAX 0 03 0 6 MIN PANEL CUTOUT 1 8 DIN 7...

Page 14: ...om the rear of the case by removing thumbnuts 3 Insert the case into the opening from the front of the panel so the gasket seals between the bezel and the front of the panel 4 Slip the sleeve over the...

Page 15: ...can reach a suitable location The antenna on this Meter and any End Devices should be installed in a vertical position pointing towards the sky Metallic structure should be kept at least 0 8 2 cm alth...

Page 16: ...m the case by pulling at the sides of the bezel 2 The bezel along with the board assembly will unlatch from the case housing Depending on the size of your Ethernet connector you may need to disconnect...

Page 17: ...rvoltage Category and pollution degree as the standard AC unit 90 240 Vac The Safety European Standard EN61010 1 for measurement control and laboratory equipment requires that fuses must be specified...

Page 18: ...outputs The SPDT Mechanical Relay SPST Solid State Relay Pulse and Analog Output Connection are shown below Figure 2 8 a Mechanical Relay and SSR b Pulse and Analog Outputs Wiring Hookup Outputs Wirin...

Page 19: ...E SSR DRIVER OUTPUT FAST BLOW FUSE 0 or 5 Vdc TYPICALLY 4 3 1 2 TEMPERATURE CONTROLLER CONTROL SIDE LOAD SIDE HEATER Vac Vac ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OU...

Page 20: ...opened Refer to Section 2 1 4 3 for assembly and disassembly instructions 2 Locate S1 jumper on the back side of the display board Select the position for your color choice of Red Green or Amber Figur...

Page 21: ...e Meter is shipped with all DIP switches in OFF position To set the Wireless and Ethernet settings to Factory Default Refer to Section 7 Figure 2 11 Location of DIP Switches 1 4 3 2 OFF ON 1 4 3 2 OFF...

Page 22: ...inout 2 2 2 10Base T Crossover Wiring When connecting the iServer directly to the computer the transmit data pins of the computer should be wired to the receive data pins of the Meter and vice versa T...

Page 23: ...room to put your IP address Figure 3 1 Label Detail 3 2 Network Protocols The Meter can be connected to the network using standard TCP IP protocols It also supports ARP HTTP WEB server DHCP DNS and Te...

Page 24: ...e only http wis03ec or any sixteen character name stored as Host Name under Access Control page from the Wireless System Home Page The default DNS name for the Meter is wis followed by the last four d...

Page 25: ...Subnet Mask of 255 255 255 0 If you are going to use a Web browser or Telnet program to access the Meter using its default IP address make sure that the PC from which you re establishing the connectio...

Page 26: ...e 192 168 1 1 as shown below and press OK Figure 3 4 Network Connections 20 Look for Internet Protocol click on it and press Properties You can access the Meter s web server via any internet browser u...

Page 27: ...IP address of 192 168 1 x that is in the same range as the Meter s default IP address 192 168 1 200 and connect to the Meter using a cross over network cable between your PC s network port and the Met...

Page 28: ...department for obtaining an IP address Figure 4 2 Assigning an IP Address using iConnect 1 Place the IP address in this box 2 Take the MAC address from the label attached to the bottom of the Meter a...

Page 29: ...ed d To access the Wireless System for Configuration Click on the View Webpage button you will access the Wireless System s home page refer to Section 4 3 for details Figure 4 3 Accessing the Wireless...

Page 30: ...ess System Home Page Select button you ll be asked for the password You should be on the Access Control page were you can simply type in the desired Static IP address and click Save For more details a...

Page 31: ...s from the MAC address label located on the Meter see Figure 3 1 if DHCP and DNS are used If a static IP address is used then simply type http x x x x where x x x x is the Meter s IP address The Home...

Page 32: ...s powered on the green LED TX will blink periodically This indicates the End Device is broadcasting its data to the Meter on channel 12 defined by IEEE 802 15 4 The LED will blink only when the End De...

Page 33: ...ion running or image of a Java logo please verify you have the latest Java Runtime Environment installed and configured according to the Section 4 3 3 1 If you do not have Java Runtime Environment you...

Page 34: ...adio signal strength 0 100 the higher the better Success 0 100 a low success rate indicates a longer data delay shorter battery lifetime and high network traffic Battery The total voltage of the batte...

Page 35: ...dialog box to show the General Tab again 4 Select the Network Settings button on the General Tab Proceed to the Browser tab Follow the Browser Proxy Selection instructions below You should either sel...

Page 36: ...e box if accessing the Meter on your local network and check the box for access from your internal network to the internet 4 Refresh or restart the webpage To disable cache setting For Java Version 1...

Page 37: ...ptions dialog and make sure that the Proxy tab shows that the Use Browser Settings option is not selected i e when you specify proxy connections in the Java Plugin control panel Accessing Meter units...

Page 38: ...shown in the file needs to be changed otherwise it will not work If more than one Meter is being monitored from the same computer it is necessary to repeat the above for each of the Meters in the sam...

Page 39: ...Data Logging and Save Current Graph buttons in the Readings and Chart pages will not be active if the instructions explained in the above Section 4 3 4 are not followed Java Runtime Settings Control...

Page 40: ...s refer to Section 4 3 3 1 If you do not have Java Runtime Environment you may download it from our website or contact the Customer Service Department nearest you Figure 4 12 Chart wiSeries Main Menu...

Page 41: ...e will disappear When clicked again it comes back to normal operation Chart Area Display the trend lines of the sensors Range of temperature can be controlled by the upper and lower boxes on the left...

Page 42: ...r Figure 4 13a Controller Setup Channel 12 Please refer to local regulation for maximum transmit power range Transmit Power Range Reset PID 13106 version x x iSeries Firmware Version x x End Device ID...

Page 43: ...local regulation for maximum transmit power range Transmit Power Range Reset PID 13106 version x x iSeries Firmware Version x x End Device ID Input Setpoints On Off Alarm 2 Analog Out Passcode ID Disp...

Page 44: ...Device specified on Device ID End Device ID Address ID of the End Device that will be display on the Meter C Transmit Power Channel 12 The Receiver communicates in a fixed channel Operation channel 12...

Page 45: ...evice ID number that will be used as input to control Filter This option allows the user to specify the number of readings stored in the Digital Averaging Filter Temperature Unit Unit of temperature r...

Page 46: ...Permanent Store Check to save Setpoints in the Meter s permanent storage On Off 1 and On Off 2 To enable and disable On Off Control Enabling On Off Controls will disable the Alarms and vice versa Dead...

Page 47: ...Off Control Setpoint 2 Permanent Store 100 DeadBand DeadBand On Off 1 On Off 2 Auto Setpoint Deviation Disabled Disabled Disabled Direct 0 Setpoint 1 0 Action Action Reverse 0 Main Menu SETUP Setpoin...

Page 48: ...you have the Analog Output Option installed in your Meter Figure 4 15b Setpoints On Off Control if Analog Output Option Setpoint 2 Permanent Store 100 DeadBand On Off 2 Disabled Direct 10 Action Main...

Page 49: ...use the temperature digits to blink in a rotating pattern If the temperature reaches the setpoint the blinking will stop otherwise the Break Alarm warning will flash and the Output will be turned off...

Page 50: ...ized under normal conditions and becomes de energized during alarm or power failure Latch if Latched Alarm remains latched until reset To reset already latched alarm select Unlatched and press Update...

Page 51: ...wer On Alarm could be triggered immediately by non controlling end device at startup Absolute Active Alarm 1 Relay Alarm 1 Low Enabled 0 Above Absolute Enabled Alarm 1 High 100 Latch Unlatched Open Ma...

Page 52: ...If the input reaches high value the output will be 0V and 0mA Voltage Current Select the output to be Voltage 0 10V or Current 0 20mA Input Low The minimum input value scaled for Output Low Output Lo...

Page 53: ...hen alarm 2 is true In order to display one color set the same display color on all three submenus If user wants the Display to change color every time when both Alarm 1 and Alarm 2 are triggered the...

Page 54: ...r the display time in seconds between each End Device Normal Choose the display color of temperature when it is in the normal stage Alarm 2 Choose the display color of temperature when alarm 2 is true...

Page 55: ...Output 2 SSR Alarm Setup Absolute Above Alarm 2 HI Value ALR H 200 Alarm 1 HI Value ALR H 400 Color Display Setup Normal Color N CLR Green Alarm 1 Color 1 CLR Amber Alarm 2 Color 2 CLR Red Display Co...

Page 56: ...is designed to monitor the Input Value around the Setpoint 2 Example 4 Output 1 Relay Setpoint 1 200 Output 2 Relay Setpoint 2 200 Alarm 1 Setup Deviation Band ALR H 20 Alarm 2 Setup Deviation Hi Low...

Page 57: ...oint ID If enabled ID Code is set to Setpoint ID Security Level and if a user attempts to enter the Configuration Menu using the Front Panel Buttons they will be prompted to enter an ID Code Full ID I...

Page 58: ...IP Address Remote Port 0 0 0 0 02000 Remote Access Disable TCP UDP Server Type TCP Command Forward CR Disable Secured Applet Title wiSeries Number of Connections 1 Port 02000 Main Menu NETWORK SETUP G...

Page 59: ...etwork host Number of Connections The range is from 0 to 5 If 0 is selected the Terminal Server feature is disabled This means that no network connection can be made to the Meter If 1 is selected only...

Page 60: ...120 0 0 0 0 120 0 F F F F F F F F F F F F F F F F 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 00...

Page 61: ...s data to the Meter Access Each check box controls whether or not readings from the End Device will be outputted If unchecked the reading from the End Device will not be displayed on the Readings and...

Page 62: ...Char Hex 0x 0000000F 0D Offset xxxx C 0 Remote Display Format Remote End Char Hex 0x 0000000F 0D Offset xxxx C 0 Device Name Update Sec ABCDEFGH 120 Display Alarm Main Menu END DEVICE PARAMETERS End D...

Page 63: ...the unit of F for a maximum of 8 characters Any letters before and or after the number will be displayed accordingly Keep in mind that the displayed letters will take away from the available 8 charac...

Page 64: ...es back to the End Device Setup page Reset Device Reset the End Device s readings and status Its data will be cleared immediately 4 3 10 Access Control This section describes the Access Control page o...

Page 65: ...the Internet The Meter s default IP address is 192 168 1 200 The Meter s IP address should be changed to fit user s networking environment Consult with your IT department for obtaining an IP address T...

Page 66: ...01i r Success rate 0 100 100 SR01j r Battery voltage mV 2810 SR01k r Device status hex msb on the left hand side 12th bit set to enable control 8th bit set to enable display 7th bit set when Open dete...

Page 67: ...y be needed with some Meters when you need to view readings from the web page while simultaneously collecting data through TCP IP communications 4 5 1 HTTPget using Port 2000 You can setup and read th...

Page 68: ...tware which may be downloaded from our website to do these IP changes whenever possible Use ARP first to assign the mac address to a static IP address in computer arp table by this command arp s 192 1...

Page 69: ...entries for specific network interface arp s plus IP address plus Physical address Use this command to manually add a permanent static entry to the ARP cache arp d plus IP address Use this command to...

Page 70: ...d the iLog software from the website listed in this manual b Install iLog software on a networked PC This software is compatible with Windows 95 98 NT 2000 and XP c For complete information of how to...

Page 71: ...th existing email that supports the MAPI messaging interface If MS OutlookTM has been loaded the MAPI support should be available 4 8 1 Installation The Mail Notifier must be loaded on a computer runn...

Page 72: ...2005 The Mail Notifier will attempt to automatically identify whether the Outlook is a newer version A red bar appears under the Mail Notifier splash window to confirm that the detection of the 2002...

Page 73: ...Notifier Commands Desired Value to Monitor Reading Command Actual Command String String see Note 2 Temperature1 Thermocouple SR a SR05a r in scale configured at Meter Temperature1 Thermocouple SR o SR...

Page 74: ...s Address Device ID Socket Number Description Src ID Reading Cmd Server IP Address 3 2000 Dev1 zRdgA 192 168 1 200 Device Info 1 of 2 Alarm Type Alarm High Alarm Low Alarm High 73 0 Info Message Email...

Page 75: ...d people 6 The FCC approval for this meter specifies the specific antenna supplied with this meter 5 1 General Deployment Guidelines 1 Position Meter in a central location When multiple End Devices ar...

Page 76: ...performance as well 10 Reduced performance scenario a A large building may have few obstructions between nodes but large amount of metallic paneling that cause reflections b A small domestic installa...

Page 77: ...communication range between the End Device and Meter Also if the antennas are mounted just barely off the ground or below the ceiling over half of the Fresnel zone ends up being obstructed resulting...

Page 78: ...mall holes in the panel or around metal edges through the process of diffraction Material Type Possible Signal Reduction Wood Plaster Sheetrock Fiberglass Uncoated Glass w out Metal 0 to 10 Brick Pres...

Page 79: ...ammable Non Isolated Retransmission 0 to 10 Vdc or 0 to 20 mA 500 max Output 1 only Accuracy is 1 of FS when following conditions are satisfied 1 Input is not scaled below 1 of Input FS 2 Analog Outpu...

Page 80: ...ification for CE are claimed External Fuse Required Time Lag IEC 127 3 recognized 100 mA 250 V 400 mA 250 V Low Voltage Power Option Time Delay UL 248 14 listed 100 mA 250 V 400 mA 250 V Low Voltage P...

Page 81: ...WIRELESS COMMUNICATION Standard IEEE 802 15 4 Frequency 2 4 GHz 2410 MHz Channel 12 Network Topology Star Topology Range UWTC 1 UWRTD 1 up to 60 m 200 ft without obstructions or interference UWTC 2 UW...

Page 82: ...Put the 8 position DIP switch 1 to ON position it does not matter if the Meter is On or Off 2 Power cycle the Meter and wait about 10 seconds until the Meter fully boots up 3 Put the DIP switch 1 back...

Page 83: ...Alarm 1 Low 100 C Alarm 1 high 4000 C Active Above C Normally Open C Latch Unlatched C Absolute Absolute C Alarm at Power On Enabled C Alarm 2 Alarm 2 Relay Enabled C Alarm 2 Low 100 C Alarm 2 high 40...

Page 84: ...D 13106 version x x iSeries Firmware Ver x x NETWORK SETUP General Secured Applet E Title wiSeries E Terminal Server TCP IP TCP E Server Type Command E Forward CR Enable E Number of Connections 1 E Po...

Page 85: ...GH 120 F 0000000F 0D F 0000000F 0D 5 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 6 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 7 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 8 ABCDEFGH 120 F 0000000F 0D F 00000...

Page 86: ...a 32 bit pattern of bits used to determine which part of the IP address is the network portion and which part is the host portion MAC Media Access Control Address is your computer s unique hardware n...

Page 87: ...pport approximately 216 65 536 computers per network The IP addresses range in binary from 10000000 00000000 xxxxxxxx xxxxxxxx to 10111111 11111111 xxxxxxxx xxxxxxxx The IP addresses range in decimal...

Page 88: ...Mask Dotted Notation Mask Binary Mask Bits Class A 255 0 0 0 Default 0 255 192 0 0 2 255 224 0 0 3 255 240 0 0 4 255 248 0 0 5 255 252 0 0 6 255 254 0 0 7 255 255 0 0 8 255 255 128 0 9 255 255 192 0...

Page 89: ...01010010 DC3 19 13 00010011 S 83 53 01010011 DC4 20 14 00010100 T 84 54 01010100 NAK 21 15 00010101 U 85 55 01010101 SYN 22 16 00010110 V 86 56 01010110 ETB 23 17 00010111 W 87 57 01010111 CAN 24 18...

Page 90: ...11 Crtl Q Data Control 1 XON SOH 01 01 Crtl A Start of DC2 18 12 Crtl R Data Control 2 Header STX 02 02 Crtl B Start of Text DC3 19 13 Crtl S Data Control 3 XOFF ETX 03 03 Crtl C End of Text DC4 20 1...

Page 91: ...007 Windows socket error Wrong IP or wrong Port number was used 10008 The Meter failed to respond to a request Wrong IP or wrong Port number was used 10011 Response came empty No data was sent 10012 D...

Page 92: ...NOTES...

Page 93: ...NOTES...

Page 94: ...NOTES...

Page 95: ...ONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications...

Page 96: ...city Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industria...

Reviews: