26
Note!
Edit these parameters at your own risk.
Edits may cause the dryer to
not
function properly. Make sure that you understand the effects that editing these
parameters will have on the dryer.
If
DRAIN
is selected the following screen will appear.
The first screen displays the drain out-put parameters. To change the drain out-put
parameters press
OK
. To increase the value press
↑
, to decrease the value press
↓
, to move
through the values press
←
and
→
. When you are satisfied with the set values press
OK
to
complete setting the parameters.
TH is the drain activation interval time. TL is drain activation duration time when the drain is
opened. Ta is the current time of the drain timer.
If
B013
is selected the following screen will appear.
The dew-point alarm can be set to ON or OFF on the last screen B013.
If
PDP
is selected the following screen will appear.
The third screen present the parameters of VARIABLE MODE PDP regulation. The desired
dew-point can be set here. In the first screen of PDP press OK and change the parameter SP
which represents the dew-point in °C. To increase the value press
↑
, to decrease the value
press
↓
, to move through the values press
←
and
→
. When you are satisfied with the set
value press
OK
to complete setting the parameter
D R A I
N
1 / 1
T H
=
1 0 :
0 0 m
T L
=
0 1 :
0 0 s
T a
=
0 0 :
0 0 m
B 0 1 3
1 / 1
O n
= - 2 5
O f
f
= - 2 5
A x
= - 4 1
P D P
1 / 3
S P
=
- 4 0
P V
=
- 1 3 0
A Q
=
+ 5
K C
=
0 .
2 0
T I
=
6 0 :
0 0 m
Summary of Contents for B-DRY Series
Page 2: ...2...
Page 15: ...15...
Page 31: ...31 5 10 Electrical Scheme Sensor Connection...
Page 35: ...35...
Page 37: ...37 Enter the password and you will get access to the controller interface...
Page 61: ...61 15 Maintenance Record TYPE OF MAINTENANCE DATE SIGNATURE NOTES Commissioned...
Page 62: ...62...
Page 63: ...63...
Page 64: ...64...