For a rapid change the operator has to keep one of the two keys (
or
) pushed for a time
longer than 2 seconds. In this case the change of parameter will be by 10 steps correspondent to
a 10 minutes a second until the release of the key.
In the case a value equal to 00.00 is set, the time of preheating is not included and the
polymerizing unit will pass directly to phase no. 2 after having reached the temperature.
Press key
to confirm data entry and pass to programming of phase no. 2.
PROGRAMMING OF BOILING (PHASE NO. 2)
The words “Ph.2”, “°C” and the last programmed boiling temperature value will appear in sequence
on the display.
The red led of
key will start flashing intermittently during all boiling program.
The change of this parameter (programming range Phase no. 1 temperature / FULL=boiling
temperature) is done by using
key (to increase value) and
key (to decrease value).
By keeping pushed one of the two keys (
or
) for a time shorter than 2 seconds, the change of
parameter will be by one step corresponding to 1 °C a press.
For a rapid change the operator has to keep one of the two keys (
or
) pushed for a time
longer than 2 seconds. In this case the change of parameter will be by 10 steps correspondent to
a 10 °C a second until the release of the key.
To make boiling, set the temperature on FULL.
Press
key to confirm entry.
If the operator has set a temperature lower or equal to 99°C then the word “rAtE” and the last
programmed speed increase value will appear on display in sequence.
If the operator has set FULL as temperature value (=boiling temperature) then the words FULL
(=max. speed) will appear on display. In this case the speed increase is automatically set at
FULL (max value).
In case the temperature of phase no. 2 is set on FULL (=boiling temperature) the speed increase
is automatically set on FULL which means the max. programmable speed (heating element always
on).
It is possible to set an increase speed different from FULL only if the set value of the
temperature set during phase no. 2 is lower or equal to 99 °C.
The modification of this parameter (programming range 0/FULL=max speed) is done by using
key
(to increase value) and
key (to decrease value.
By keeping pushed one of the two keys (
or
) for a time shorter than 2 seconds, the change of
parameter will be by one step corresponding to 1 unit a press.
For a rapid change the operator has to keep one of the two keys (
or
) pushed for a time
longer than 2 seconds. In this case the change of parameter will be by 10 steps correspondent to
a 10 units a second until the release of the key.
It is advisable never to set the speed increase on a value inferior to 17 otherwise the heating
will be too slow.
Press
key to confirm entry.
The word “Hr.Mn” followed by the last programmed holding time will appear on display.
Four numbers separated by a dot will appear on display.
The two still numbers on the left side of the dot show the hours, while the flashing numbers on
the right side of the dot show the minutes.
The first parameter to change are the hours.
The modification of this parameter (programming range 00/20 hours) is done by using
key (to
increase value) and
(to decrease value) key.
- Page 5/9 -