The maximum possible configuration  consists of one BS-114 control keyboard, 4  BS-
116 panels ,  three  BS-115 repeaters, 4 BS-117 relay devices 

and

 8 BS-118 extinguishing 

devices. Each device has it’s own address number. The connection between all of these 
devices is shown in figure 2. Each panel can also accept a  BS-620 

m

egaphone driving 

device. 
Any configuration between the minimum and maximum described is possible. In this way 
a fire detection panel with the required capabilities can be configured.   

 Figure 2

BS-116

panel

No 1

BS-116

panel

No 2

BS-116

panel

No 3

BS-116

panel

No 4

Control 

keyboard

BS-114

Repeater

BS-115

No 1

Repeater

BS-115

No 2

Repeater

BS-115

No 3

BS-117

16 relay device

No 1

BS-117

16 relay device

No 2

BS-117

16 relay device

No 3

BS-117

16 relay device

No 4

230V

AC

BS-118

fire 

extinguishing 

device

No 1

BS-118

fire

extinguishing

device

Nï 2

BS-118

fire

extinguishing

device

No 8

Date

File

Code

Page

09-

E

1116000.09-

E

4 from 20

Date

File

Code

Page

09-

E

1116000.09-

E

3 from 20

1. Preface

A fully integrated fire detection system consisting of independent modules is a new idea 
in the safety systems area. A group of 6 different devices can be combined with various 
ways in order to realize a 16 to 64 zone fire detection systems with the capability to 
monitor and drive extinguishing devices, electro valves, electromagnetic door latches 
and all the devices that are needed to build even the most complicated fire detection 
system. The programming and monitoring of these devices is done using a single control 
device. This is the only device that must be in the control area.

2. Device types

The system consists of the following device types :

BS-116

16 zone fire detection panel
Keyboard- fire detection control and programming device
Indication device (repeater)
16 Relay device
Extinguishing device with adjustable delay
Public-address megaphone device with microphone

Type

Description

BS-114
BS-115
BS-117
BS-118
BS-119

3. Configuration selections

The minimal required devices needed in order to develop a fully operational fire 
detection system are a Bs116 fire detection panel and a Bs114 control and programming 
keyboard. These devices are connected with 4 cables as shown in figure 1. The maximum 
cable length must not exceed 500 metres.

A
A

29

30

31

32

1

2

3

4

A

A

BS-114

Programming and 

control keyboard

B

S

-1

1

6

F

ir

e

 d

e

te

c

ti

o

n

 p

a

n

e

l

Figure  1

22 

December

 2004

22 

December

 2004

Summary of Contents for BS-116

Page 1: ...ITAL FIRE DETECTION PANEL CONTENTS 1 Preface 2 Device Types 3 Configuration selections 4 Connections 5 Starting configuration Setup 6 Operation procedures 6 1 Operation level 1 6 2 Operation level 2 6...

Page 2: ...the safety systems area A group of 6 different devices can be combined with various ways in order to realize a 16 to 64 zone fire detection systems with the capability to monitor and drive extinguish...

Page 3: ...that the polarity is right SIREN 1 SIREN 2 5 6 5 6 Terminal resistor Terminal resistor BS 531 Sounder with beacon GND 12V 24V BS 531 Sounder with beacon GND 12V 24V BS 531 Sounder with beacon GND 12V...

Page 4: ...E 1116000 09 E 8 from 20 GENERAL SYSTEM RESET 15 Enter the code 9999 and the device will start the automatic recognition procedure and the Display shows in sequence SEARCHING UNIT SCI POINT XX Every...

Page 5: ...gized o silence the buzzer and the sirens press the ON OFF BUZZER To silence nly the sirens press the ENTER key and enter the user code In order to RESET the system when the sirens are silenced press...

Page 6: ...6000 09 E 12 from 20 7 Programming tests information Press the ENTER button The Display shows Then press the 1 key four times The Display shows And we have entered in the technician menu After this we...

Page 7: ...same as described earlier for the ALARM relay With the option DURATION we can select if the output will have a permanent or an interruptible operation The settings are the following Date File Code Pa...

Page 8: ...e development date is the 12th month of the year 2000 Date File Code Page 09 E 1116000 09 E 16 from 20 Programming zone relays If a BS 117 relay module is connected we can select CONFIGURE RELAY 1 64...

Page 9: ...Deactivation The fourth selection on the technicians menu is If ENTER is pressed then we enter the deactivation submenu of the system Through this menu we can deactivate the operation of the zones an...

Page 10: ...RM CIRCUITS OUTPUTS OPERATION RANGE PRODUCED IN ACCORDANCE WITH CONSTRUCTION MATERIAL DIMENSIONS WEIGHT GUARANTEE TECHNICAL CHARACTERISTICS ENABLE SIREN 1 With the numeric keypad and the ENTER key sel...