4. Connections
All connection
s
to the panel must be made before connecting the battery and the
mains power supply.
Each panel has terminal blocks for connecting 16 zones of detectors, break-glass call points
or other input devices. Each zone terminal block has a pre-fitted terminal resistor (5K6). This
resistor is removed and placed on the last device of the zone or it is left in it’s place if the
zone is not used.
The connections for all 16 zones are identical. What it show in figures 4 and 5 for zone 1 is
also valid for all the other zones.
1
2
3
5
4
Figure
4.
Connecting
1
manual call point
BS-536
and
1
detector base on
zone
1
and
connecting
2
bases of
detectors on
zone
2.
One detector also has a BS-572 remote LED indicator connected to it.
Detector
base
Detector
base
5
Κ
6
IN
IN
OU
T
O
U
T
R
IN
IN
OU
T
O
U
T
R
Remote
LED
BS-572
R
Terminal
resistor
Detector
base
IN
IN
OU
T
O
U
T
R
Manual call
point
BS-536
OUT
IN
5
Κ
6
Terminal
resitor
FUSE
5x20 3A
L
N
L
N
2
3
0
V
~
Figure
3.
Connection diagram with the mains voltage
.
ΖΟΝΕ 1
ΖΟΝΕ 2
GND
6
from
21
921116000
Date
File
Code
Page
5
Κ
6
1
2
3
4
24 Vdc
monitor
ZO
NE
10
-3
0V
NC
NO
C
ZO
NE
10
-3
0V
NC
NO
C
ZO
NE
10
-3
0V
NC
NO
C
Figure
5.
Connecting
3
gas detectors
BS-685
or
BS-686.
Besides connecting
these detectors to the
zone we must
also power them from the
24V
dc
monitor
output
.
Terminal
resistor
Gas
detector
BS-675
Gas
detector
BS-675
Gas
detector
BS-675
921116000_09_016
13/03/2013