LB51100 Installation and User Manual 

17 

Shenzhen Olipower Energy & Automation Technology., Ltd 

 

 

will not be extinguished immediately. Slave battery boxes fault lights 

flashing after 10s, slave battery boxes RUN lights and fault lights extinguished after 1min, the parallel Batteries 

system shut down in normal. 

NOTICE

 

When the battery box is in parallel, press the power button of the battery box will shut down the battery box. In 

normal use, we strongly recommend that you do not only turn off a battery box as a slave machine.The remote 

monitoring of battery is available via inverter monitoring solution. 

7

 

Battery box abnormal and solution 

 

Abnormal 

description 

Abnormal 

interpretation 

 

Phenomenon 

 

Cause 

 

solution 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Run indicator 

light, 

Fault indicator 

light, battery 

no voltage 

output 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Function 

of 

battery 

self-
protection 

 

The low battery indicator 

is light, and the fault 

indicator is light. The 

battery box has no 

output. 

 
 
 

 

The battery is too low 

The battery must be charged at once, and the 

specific operation will refer to the low power 

charge function. 

Check the communication between the battery 

box and the inverter is 

normal. 

 
 
 
 
 
 
 
 

 

When the battery box is 

running, fault indicator 

lights up. 

 

 

The battery is too 

high 

The battery must be stopped charging 

immediately. 

Check the communication between 

the battery box and the inverter is normal. 

 
 

 

The current is too 

large 

Please refer to the parameters of the battery 

charging current and discharge current of the 

corresponding model, and compare the 

technical parameters of the 

inverter. 

 

The temperature is too 

high 

Please install the battery in a ventilated 

place, which is beneficial 

to the heat dissipation of the battery. 

The temperature is too 

low 

Please pay attention to the battery 

box to keep warm in the cold area. 

 
 
 
 
 

Incorrect 

use of 

battery 

 

After starting, the fault 

indicator is light. 

 

Incorrect setting of 

DIP switch 

Check whether the battery box DIP switch is 

set correctly. If it is not correct, please refer 

to the use 

manual to set the DIP switch. 

When the battery is used 

in parallel, the fault 

indicator of the slave 

station battery box is light, 

and there is no 

fault when the battery 

 
 

 

Incorrect setting of 

DIP switch 

Check whether the communication 

connection between the main and slave 

stations of the battery box is firmly 

connected. Check whether the DIP switch 

of the battery main 

station and the slave station is set 

Summary of Contents for LB51100

Page 1: ...LB51100 Installation and User Manual 1 Shenzhen Olipower Energy Automation Technology Ltd LB51100 Installation and User Manual Version V1 0...

Page 2: ...Introduction 6 4 2 Identifying The Product 6 4 3 Maintenance and Replacement 6 5 System Installation 7 5 1 Installation notice 7 5 2 Package information and system configuration list 7 5 2 1 Parts li...

Page 3: ...Battery box activate and shutdown 14 6 1 Panel buttons and LEDs meaning 14 6 2 The operation steps of the battery box works alone 14 6 2 1 Start battery box 14 6 2 2 Shut down battery box 14 6 2 3 Lo...

Page 4: ...Shenzhen Olipower Energy Automation Technology Ltd Due to product upgrades or other reasons this document will make appropriate adjustments Unless otherwise agreed this document is intended to be used...

Page 5: ...s Manual This is the Manual for the low voltage 48V residential rack battery products User of this device or installer must refer to the installation guidance to installation and using correctly 2 2 U...

Page 6: ...following precautions is not fully understood or has any problems please contact the customer service officer for assistance The safety part may not include all the regulations in your area The use of...

Page 7: ...ill the regulations and legal enquiry The user has the responsibility and obligation to send it to the designated organization for recycling and disposal 5 System Installation 5 1 Installation notice...

Page 8: ...ed in cartons and the components assort with the battery case When you confirm the good s please read the configuration list carefully to make sure that the battery box and kit are intact 5 2 1 Parts...

Page 9: ...e to side along the wall until the mounting card on the battery box is placed in the proper position of the rack mounting position Information Rack mounted installation is suggested that the external...

Page 10: ...as a parallel battery B B Battery negative The two negative are the same one of which can be used as a parallel battery B Attention B interface RJ45 port corresponding to the CAN bus pin definition R...

Page 11: ...drawing is for reference only please take the material as the standard It is an Australia installation standard requirement AS NZS 5139 that an overcurrent protection and isolation device that operat...

Page 12: ...tch after the need to restart the battery box restart the settings will take effect Single battery box through the LINK communication connection to the inverter when the address DIP switch defined as...

Page 13: ...1 and slave battery box 2 if have slave battery box 2 Step 4 After the battery is completed in parallel it is suggested that you wait a few minutes to connect the inverter later 5 4 3 2 The connection...

Page 14: ...the DIP switch is defined as follows CAUTION Set the DIP switch after the need to restart the battery box restart the settings will take effect Three battery boxes in parallel when the DIP switch is...

Page 15: ...FF Turn on or off button Control battery box on or off RUN Running indicator light green When the battery box is running normally it always bright LOW BAT Low battery indicator yellow When the battery...

Page 16: ...off run LED no longer flashing just on after 90S means the battery into the normal charging mode the battery is not detected charging after 90S the fault red LED will flashing the battery cannot be r...

Page 17: ...attery box and the inverter is normal When the battery box is running fault indicator lights up The battery is too high The battery must be stopped charging immediately Check the communication between...

Page 18: ...t Short circuit cause damage of battery box fuse Check whether the connection is correct and whether there is a short circuit If there is a short circuit please check the cause as soon as possible and...

Page 19: ...weight 46 2kg Installation method Rack mounting Cycle times 80 DOD 25 4000 Charge temperature range 0 55 Discharge temperature range 20 55 communication interface CAN2 0 LINK Modbus RS485 Battery pro...

Page 20: ...LB51100 Installation and User Manual 20 Shenzhen Olipower Energy Automation Technology Ltd Appendix 2 Product size table Product model Outline dimension LB51100...

Reviews: