LB51100 Installation and User Manual
17
Shenzhen Olipower Energy & Automation Technology., Ltd
will not be extinguished immediately. Slave battery boxes fault lights
flashing after 10s, slave battery boxes RUN lights and fault lights extinguished after 1min, the parallel Batteries
system shut down in normal.
NOTICE
:
When the battery box is in parallel, press the power button of the battery box will shut down the battery box. In
normal use, we strongly recommend that you do not only turn off a battery box as a slave machine.The remote
monitoring of battery is available via inverter monitoring solution.
7
Battery box abnormal and solution
Abnormal
description
Abnormal
interpretation
Phenomenon
Cause
solution
Run indicator
light,
Fault indicator
light, battery
no voltage
output
Function
of
battery
self-
protection
The low battery indicator
is light, and the fault
indicator is light. The
battery box has no
output.
The battery is too low
The battery must be charged at once, and the
specific operation will refer to the low power
charge function.
Check the communication between the battery
box and the inverter is
normal.
When the battery box is
running, fault indicator
lights up.
The battery is too
high
The battery must be stopped charging
immediately.
Check the communication between
the battery box and the inverter is normal.
The current is too
large
Please refer to the parameters of the battery
charging current and discharge current of the
corresponding model, and compare the
technical parameters of the
inverter.
The temperature is too
high
Please install the battery in a ventilated
place, which is beneficial
to the heat dissipation of the battery.
The temperature is too
low
Please pay attention to the battery
box to keep warm in the cold area.
Incorrect
use of
battery
After starting, the fault
indicator is light.
Incorrect setting of
DIP switch
Check whether the battery box DIP switch is
set correctly. If it is not correct, please refer
to the use
manual to set the DIP switch.
When the battery is used
in parallel, the fault
indicator of the slave
station battery box is light,
and there is no
fault when the battery
Incorrect setting of
DIP switch
Check whether the communication
connection between the main and slave
stations of the battery box is firmly
connected. Check whether the DIP switch
of the battery main
station and the slave station is set