LB51100 Installation and User Manual
18
Shenzhen Olipower Energy & Automation Technology., Ltd
box is used alone.
correctly. If incorrect, please refer
to the manual to set up the DIP
switch.
When the battery box is
in parallel for the first
time, start the parallel
system. The fault
indicator of the slave
station battery box is
light, and the slave
station has no voltage
output.
Protection measures
to prevent battery
damage when the
battery is in parallel.
Take the positive and negative
voltage of each battery box. If the
voltage difference between the
battery boxes is more than 2V,
please keep the pressure difference
under 2V and try the parallel
connection.
Run indicator
light,
Fault indicator
not light,
battery no
voltage output
Battery device
damage
The battery has no fault
alarm, but there is no
voltage output
Short circuit cause
damage of battery box
fuse
Check whether the connection is
correct and whether there is a short
circuit. If there is a short circuit,
please check the cause as soon as
possible and solve the short circuit
problem, and then change the fuse
with the after sale or professional.
Battery internal
device damage
Please contact the after-sale service
Press the
battery button,
all the battery
indicators are
not light
The battery indicator is
not light and the battery
has voltage output
The battery indicator
is damaged, the line is
loose, or aging.
Please contact the after-sale service
The battery indicator is
not light and the battery
has no voltage output
Circuit board fault,
circuit board wiring
looseness or aging.
Please contact the after-sale service
Other
anomalies
Please contact the after-sale service
8
Battery box compatible with the inverter
Serial
number
Inverter brand
Inverter model
1
SMA
Sunny Island
2
SolaX
X-Hybrid
3
Goodwe
ES-series
4
SofarSolar
ME 3000SP
5
MUST
PH&PV series