Parameter
DISPLAY
MNEMONIC
MENU
Range of
ad
M
ustment
Factory
setting
COMMENTS
COOLING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
Cc1
Service
-15 – +50°C
20°C
Factory settings for
fan coils and control of
systems with leaving
water temperature
(LUc 1)
Cc3 Cc1; Cc2 Cc4
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
Cc2
Service
Luc 0:
4°C -20°C,
Luc 1:
7°C -27°C
18°C
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
Cc3
Service
-15 – +50°C
40°C
COOLING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
Cc4
Service
Luc 1:
4°C -20°C,
Luc 0:
7°C -27°C
15°C
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
Hc1
Service
-15 – +50°C
-5°C
Factory settings for
fan coils and control of
systems with leaving
water temperature
(LUc 1)
Hc3 Hc1; Hc2 Hc4
HEATING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
Hc2
Service
Luc 1:
20-60°C,
Luc 0:
20-55°C
35°C
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
Hc3
Service
-15 – +50°C
20°C
HEATING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
Hc4
Service
Luc 1:
20-60°C,
Luc 0:
20-55°C
28°C
SERVICE MENU
PASSWORD
PAS
Service
Value held by Olimpia
Splendid Service
rtF
Service
0 – 200
(step 10)
0
FACTOR USE, DO
NOT MODIF
PERIPHERAL ADDRESS
Adr
Service
1 – 255
1
RS485 communication
port address to be used
with any remote control
peripheral (PC or the
like)
Summary of Contents for BIG
Page 2: ...2 1 3 2 A M L O N R H G Q I B E D P F C K ...
Page 3: ...3 5 4 6 A B C A B ...
Page 4: ...4 8 D D D D C D A D H G G I F E B D 9 30cm 60 cm 30 cm 15 cm 30 cm 60cm L A A 7 ...
Page 6: ...6 17 16 A B E F E G H C D 18 15 14 C D A B A H B C D E F E G ...
Page 8: ...8 24 23 22 ...
Page 11: ...11 ...
Page 35: ......
Page 59: ......
Page 83: ......
Page 107: ......
Page 108: ...www olimpiasplendid it info olimpiasplendid it 277228C ...