44
ENGLISH
T
K
e minimum nominal diameter of t
K
e
K
ydraulic connecting pipes must be 1”.
To allo
Z
t
K
e maintenance and repair operations it is indispensable t
K
at eac
K
K
ydraulic connection is
¿
tted
Z
it
K
respec-
tive manual closing valves.
The table below shows the characteristics the hydraulic system must have.
Unit
OS-CEBSH24EI OS-CEBCH36EI
OS-CEBCH48EI
OS-CEBTH48EI
OS-CEBCH60EI
OS-CEBTH60EI
I.U. SHERPA SMALL
I.U. SHERPA BIG
Nominal water
ow*
l/s
0,31
0,52
0,62
0,62
0,69
0,79
System water
content
Min
l
23
38
45
45
51
58
Max**
l
400
400
400
400
400
400
Operating
pressure
Max
kPa
300
300
300
300
300
300
System height
difference
Max
m
20
20
20
20
20
20
*
for systems at ground level
**
with maximum system water temperature 35°C
The graphs in g. 19 show the head, for each hydraulic circulator speed, available to the hydraulic connections of the internal unit.
Check that the system’s pressure losses guarantee the required water ow (see sect. 2.10.2).
If greater heads are required due to high pressure losses in the system, an inertial vessel or a hydraulic separator and an external
idle pump must be added.
Check if the system has the minimum water content required to ensure good system operation. If it is insuf cient, add a storage
vessel in order to reach the required content.
The water distribution pipes must be suitably insulated with expanded polyethylene or similar materials. The on/off valves, bends
and unions must also be suitably insulated.
To prevent air locks inside the circuit, insert automatic or manual breather devices at all the points (high pipes, traps etc.) where
air may accumulate.
Once t
K
e
K
ydraulic circuit is complete and t
K
e absence of lea
N
s
K
as been ascertained, remove t
K
e circulation pump
brac
N
et (
¿
g. 20 ref. A) by removing t
K
e fastening nut (
¿
g. 20 ref. B); re
¿
t t
K
e nut.
2.5.1 Hydraulic
circuit
( g. 21)
The hydraulic diagram in g. 21 shows the main parts of the internal unit and a typical hydraulic circuit.
1
Water inlet
2
Safety valve (3 bar)
3
Pressure
gauge
4
System water return temperature probe T1
5
Plate heat exchanger
6
System water ow temperature probe T2
7
Flow
switch
8
Expansion
vessel
9
Electrical heater elements collector
10
Automatic air breather
11
Circulation
pump
12
3-way diverter valve (integrated on board the machine in version 3W)
13
System water outlet
14
Water outlet for domestic water storage
15
Mesh
water lter
16
Refrigerant pipe connections
17
Domestic heater temperature probe T3
A
Internal
unit
B
External
unit
C
System (fan coils, radiators or radiant panels/ oors)
D
Domestic water storage
E
Additional heat source (e.g. gas boiler)
Install a sieve lter with 0.4 mm mesh on the appliance’s water inlet pipe (return from system).
2
Summary of Contents for BIG
Page 2: ...2 1 3 2 A M L O N R H G Q I B E D P F C K ...
Page 3: ...3 5 4 6 A B C A B ...
Page 4: ...4 8 D D D D C D A D H G G I F E B D 9 30cm 60 cm 30 cm 15 cm 30 cm 60cm L A A 7 ...
Page 6: ...6 17 16 A B E F E G H C D 18 15 14 C D A B A H B C D E F E G ...
Page 8: ...8 24 23 22 ...
Page 11: ...11 ...
Page 35: ......
Page 59: ......
Page 83: ......
Page 107: ......
Page 108: ...www olimpiasplendid it info olimpiasplendid it 277228C ...