To set the parameters see the table below that summarises the parameters.
Example:
Press
ey4
, to view USr on the display
Press
ey6
, to view the rst parameter hrS (clock hour setting)
Press
ey6
, to view the parameter value (e.g.: 10)
Press
ey6
for three seconds, the parameter value ashes on the display
Press
ey1
/ ey2
to increase or reduce the parameter value displayed
Press
ey6
, to con rm the set value, the display stops ashing
Press
ey4
, to exit and view the parameter
Press
ey1
or ey2
to change parameter and proceed as above to change other parameters
Press
ey1
and ey2
simultaneously to quit the user menu
Parameter
DISPLAY
MNEMONIC
MENU
Range of
ad
M
ustment
Factory
setting
COMMENTS
S STEM CLOC :
HOUR SETTING
h S
User
0-23
0
S STEM CLOC :
MINUTE SETTING
in
User
0-59
0
TIMER ACTIVATION/
DEACTIVATION
0 timer deactivated
1 timer activated
ti
User
0-1
0
S STEM START TIME
StA
User
00.0 – 23.5
0.00
Decimals tens of minutes,
e.g.: 0.1 10 minutes, 0.5 50
minutes
S STEM SHUTDOWN
TIME
Sto
User
00.0 – 23.5
0.00
Decimals tens of minutes,
e.g.: 0.1 10 minutes, 0.5 50
minutes
NIGHT-TIME MODE
ACTIVATION/
DEACTIVATION
0 night-time mode
deactivated
1 night-time mode
activated
ncL
User
0,1
0
The yield and the maximum
noise level are reduced
NIGHT-TIME MODE
SWITCH-ON TIME
nSt
User
00.0 – 23.5
0.00
Decimals tens of minutes,
e.g.: 0.1 10 minutes, 0.5 50
minutes
NIGHT-TIME MODE
SHUTDOWN TIME
nSP
User
00.0 – 23.5
0.00
Decimals tens of minutes,
e.g.: 0.1 10 minutes, 0.5 50
minutes
Inlet water temperature
t1
Temperature/
Set
Outlet water
temperature
t2
Temperature/
Set
Domestic water tank
sensor temperature
t3
Temperature/
Set
Outside air sensor
temperature
t4
Temperature/
Set
Compressor operating
hours
CHC
Temperature/
Set
COOLING SET-POINT
1
cS1
Temperature/
Set
User
Luc 0: 7°C
- 25°C
Luc 1: 4°C
- 20°C
Luc 0: 20°C
Luc 1: 15°C
Factory settings for radiant
oors
COOLING SET-POINT
2 (Eco Mode)
cS2
Temperature/
Set
User
Luc 0: 7°C
- 25°C
Luc 1: 4°C
- 20°C
Luc 0: 23°C
Luc 1: 18°C
Factory settings for radiant
oors
HEATING SET-POINT
1
HS1
Temperature/
Set
User
Luc 0: 20°C
- 55°C
Luc 1: 20°C
- 60°C
Luc 0: 30°C
Luc 1: 35°C
Factory settings for radiant
oors
Summary of Contents for BIG
Page 2: ...2 1 3 2 A M L O N R H G Q I B E D P F C K ...
Page 3: ...3 5 4 6 A B C A B ...
Page 4: ...4 8 D D D D C D A D H G G I F E B D 9 30cm 60 cm 30 cm 15 cm 30 cm 60cm L A A 7 ...
Page 6: ...6 17 16 A B E F E G H C D 18 15 14 C D A B A H B C D E F E G ...
Page 8: ...8 24 23 22 ...
Page 11: ...11 ...
Page 35: ......
Page 59: ......
Page 83: ......
Page 107: ......
Page 108: ...www olimpiasplendid it info olimpiasplendid it 277228C ...