14

 

2.3.

 

To exit while viewing a menu (ECHAP) 

Simultaneously  press  the  +  and  -  keys  and  validate  or  don’t  validate  the  recording  of  potentially 
modified parameters: 
 

-

 

press ENTER to abort without any change  

-

 

press «+», then ENTER to exit by validating the changes. 

 
 

2.4.

 

Programming menu   

 
A maintenance key                     is displayed while using the programming menu  
 

 

This allows programming of parameters of the measuring channel such as: 

-

 

On/off: yellow DEL is blinking 

-

 

Detected gas chemical symbol (CH4 /CO, etc.) 

-

 

Measuring unit (%LEL/ppm, etc.) 

-

 

Measuring scale and decimal point (0.1/1.0/10/100/1000, etc.) 

-

 

Programming  of  two  gas  alarm  thresholds  (characteristics):  corresponding  red  DEL  is  on 
during this step  

-

 

Selecting the erasure type of gas alarms  

1.

 

manual  (MAN)  =  if  the  gas  concentration  again  becomes  lower  than  the 
preset  alarm  threshold,  this  alarm  must  be  acknowledged  manually  by 
pressing the acknowledgment key              

 
 

2.

 

or  automatical  (AUT)  =  if  the  gas  concentration  again  becomes  lower 
than the preset alarm threshold, the acknowledgment is automatic. 

 

-

 

Timing (in minutes and seconds) of the alarm relay activation time: yellow DEL is blinking 

MA

 

 
 
 
 
 
 
 
 

-

 

Timing  (in  minutes  and  seconds)  of  the  fault  relay  activation  time:  yellow  DEL  is  on 
continuously  

-

 

Timing of the central unit upon activation (relays disabled): yellow DEL is blinking and the 
following icon            is displayed. 

 
-

 

Indicating the type of sensor used, such as: 

 

Bridge: in bridge (filaments), types OLC10, CEX300, etc. 

 

EHP: EXPLO (explo. 4/20mA), type OLCT10, etc. 

 

 InC: fire (ionic, optical, etc.) 

 

O2: oxygen 

 

Aut: other (toxic, etc.) 

Exceeding alarm 
threshold 

 

DEL 
Alarm 
and Buzzer 

Timing 
 

AL relay  
cutover 
 

Diagram of alarm activation  

 

Summary of Contents for MX15

Page 1: ...I IN NS ST TA AL LL LA AT TI IO ON N A AN ND D O OP PE ER RA AT TI IN NG G I IN NS ST TR RU UC CT TI IO ON NS S Ref NPM15GB...

Page 2: ...uired particularly for electrical installation and assembly connections service lines Any modification of the equipment as well as use of unauthorized parts will result in cancellation of any warranty...

Page 3: ...ECIFIC USE C C L L A A U U S S E E S S C C O O N N C C E E R R N N I I N N G G P P R R O O P P E E R R T T Y Y Drawings plans specifications and information included in this document contain confident...

Page 4: ...ly 230 Volts 115VAC on request 11 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 24V as indicated in the wiring examples at the end of the manual 11 2 3 Measuring...

Page 5: ...otentiometers A motherboard including all system components power supply display relays and connectors A front face with tactile keys I I I I T T e e c c h h n n i i c c a a l l s s p p e e c c i i f...

Page 6: ...ammable Display front Type LCD screen 4 digits 7 segments 3 characters 14 icon segments 4 LEDs Description of unit and gas programmable by user in a list 3 characters edited by user Keyboard through t...

Page 7: ...h information provided to external units The site manager where the equipment is installed should take into consideration and comply with the information in the following paragraphs Refer to the provi...

Page 8: ...l unit in configuration 0 at 100 LEL The following curve provides a response to the central unit regarding the measured value and fault processing based on the value of the input current supplied by t...

Page 9: ...n attended area control centre console room control room etc and in a less humid no condensation and temperate environment see chapters 2 1 and 3 2 2 C Ce en nt tr ra al l u un ni it t e el le ec ct t...

Page 10: ...should be wired on the two terminals L orange and N blue as indicated in the wiring examples at the end of manual 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 2...

Page 11: ...e in positive safety negative upon request and potential free REL1 terminals match the relay 1 contacts alarm 1 REL2 terminals match the relay 2 contacts alarm 2 The relay contacts can be used normall...

Page 12: ...replaced with an interrupted line on the display unit To return to the measurement display press one of the two keys or To return to normal operation simultaneously press the and keys 2 2 M Me en nu u...

Page 13: ...larms 1 manual MAN if the gas concentration again becomes lower than the preset alarm threshold this alarm must be acknowledged manually by pressing the acknowledgment key 2 or automatical AUT if the...

Page 14: ...changes the access code for various menus 1000 in standard upon shipment of equipment display the CODE menu and key validate it enter display current code indicate the new code using the and keys vali...

Page 15: ...s concentration is correct by reading the display unit Otherwise adjust the sensitivity using a S potentiometer Disconnect the standard gas cylinder Wait for the return to zero on the display unit Pre...

Page 16: ...intended to be a measure of the accuracy of the instrument Industrial scientific further recommends that a full instrument calibration be performed using a certified concentration s of calibration ga...

Page 17: ...onal use of natural resources MX15 has to be the object of a selective collection for the electronic equipments and cannot be scrapped with the normal domestic waste The user thus has the obligation t...

Page 18: ...gment 1 3 relay contact outputs potential free NO or NF based on position of jumpers next to relays DEF RL1 RL2 Connector of first sensor with 2 wires Example of connection between a MX15 central unit...

Page 19: ...0 TWIN type sensors L N T MAINS 230VAC 0 24V Remote acknowledgment 1 2 3 Connector of first sensor with 3 active wires relay contact outputs potential free NO or NF based on position of jumpers next t...

Page 20: ...ring 1 2 3 1 2 3 Example of connection with an EXPLO or TOXIC sensor with 3 active wires L N T MAINS 230VAC 0 24V relay contact outputs potential free NO or NF based on position of jumpers next to rel...

Page 21: ...22...

Page 22: ...23 Ex Ox Tox Gasdetectie Westerdreef 5V 2152 CS Nieuw Vennep Telefoon 0252 620885 E mail info exoxtox n Website www exoxtox nl...

Reviews: