background image

 

16

INDUSTRIAL SCIENTIFIC recommends:  
 

Calibrate  the  sensor  connected  to  the  MX15  central  unit  at  least  once  a  year,  then  based  upon 
environmental conditions (T°, dust, vibrations etc.). It is also recommended to calibrate the detector 
upon exposure to high gas concentrations. 

 

Reminder: for safety purposes, only authorized and trained people are allowed 
to use the following menus.

 

 

 

Procedure to be followed when the MX15 central unit is connected to an explosive gas sensor  

(OLC10/CEX300, etc.): 

 

-

 

the TEST menu was validated (see above) 

-

 

remove the small cover on the front of MX15 to access the setting potentiometers 

-

 

adjust, if needed, the ZERO (read the display unit) using a zero potentiometer «O» 

 
 
Reminder: make sure that you have clean air - otherwise inject air or nitrogen on the sensor 
(with calibration kit) with a flow rate of 60 l/h, then wait for the stabilisation of measurement 
 

-

 

Now inject the standard gas (60l/h) on the sensor and wait for the measurement stabilisation 

-

 

Make sure that the gas concentration is correct by reading the display unit 

-

 

Otherwise, adjust the sensitivity using a “S” potentiometer  

-

 

Disconnect the standard gas cylinder  

-

 

Wait for the “return to zero” on the display unit  

-

 

Press the TEST key to exit this menu 

-

 

The yellow “DEL” is off and the display unit indicates an interrupted line 

-

 

Press one of the two keys + or – to display the measurement, if needed 

-

 

Position the small cover in place. 

 
 
 

Procedure to be followed when a MX15 central unit is connected to a transmitter 4-20 mA 

without local maintenance device (calibration position switch, etc.) : 

 

-

 

the TEST menu was validated to disable the relays of the central unit: see the beginning of 
this chapter  

-

 

adjust the transmitter (see manual of relevant product) 

-

 

make sure that the transmitter instructions (O and S) match those of the central unit.  Refine 
the  adjustments,  if  needed,  of  the  central  unit  and,  in  this  case,  refer  to  the  previous 
paragraph 

-

 

upon  completion  of  calibration,  wait  for  the  «return  to  zero»  on  the  display  unit  of  the 
central unit  

-

 

Press the TEST key to exit this menu  

-

 

Yellow “DEL” is off and the display unit shows an interrupted line 

-

 

Press one of the two keys + or – to display the measurement, if needed. 

 

Summary of Contents for MX15

Page 1: ...I IN NS ST TA AL LL LA AT TI IO ON N A AN ND D O OP PE ER RA AT TI IN NG G I IN NS ST TR RU UC CT TI IO ON NS S Ref NPM15GB...

Page 2: ...uired particularly for electrical installation and assembly connections service lines Any modification of the equipment as well as use of unauthorized parts will result in cancellation of any warranty...

Page 3: ...ECIFIC USE C C L L A A U U S S E E S S C C O O N N C C E E R R N N I I N N G G P P R R O O P P E E R R T T Y Y Drawings plans specifications and information included in this document contain confident...

Page 4: ...ly 230 Volts 115VAC on request 11 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 24V as indicated in the wiring examples at the end of the manual 11 2 3 Measuring...

Page 5: ...otentiometers A motherboard including all system components power supply display relays and connectors A front face with tactile keys I I I I T T e e c c h h n n i i c c a a l l s s p p e e c c i i f...

Page 6: ...ammable Display front Type LCD screen 4 digits 7 segments 3 characters 14 icon segments 4 LEDs Description of unit and gas programmable by user in a list 3 characters edited by user Keyboard through t...

Page 7: ...h information provided to external units The site manager where the equipment is installed should take into consideration and comply with the information in the following paragraphs Refer to the provi...

Page 8: ...l unit in configuration 0 at 100 LEL The following curve provides a response to the central unit regarding the measured value and fault processing based on the value of the input current supplied by t...

Page 9: ...n attended area control centre console room control room etc and in a less humid no condensation and temperate environment see chapters 2 1 and 3 2 2 C Ce en nt tr ra al l u un ni it t e el le ec ct t...

Page 10: ...should be wired on the two terminals L orange and N blue as indicated in the wiring examples at the end of manual 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 2...

Page 11: ...e in positive safety negative upon request and potential free REL1 terminals match the relay 1 contacts alarm 1 REL2 terminals match the relay 2 contacts alarm 2 The relay contacts can be used normall...

Page 12: ...replaced with an interrupted line on the display unit To return to the measurement display press one of the two keys or To return to normal operation simultaneously press the and keys 2 2 M Me en nu u...

Page 13: ...larms 1 manual MAN if the gas concentration again becomes lower than the preset alarm threshold this alarm must be acknowledged manually by pressing the acknowledgment key 2 or automatical AUT if the...

Page 14: ...changes the access code for various menus 1000 in standard upon shipment of equipment display the CODE menu and key validate it enter display current code indicate the new code using the and keys vali...

Page 15: ...s concentration is correct by reading the display unit Otherwise adjust the sensitivity using a S potentiometer Disconnect the standard gas cylinder Wait for the return to zero on the display unit Pre...

Page 16: ...intended to be a measure of the accuracy of the instrument Industrial scientific further recommends that a full instrument calibration be performed using a certified concentration s of calibration ga...

Page 17: ...onal use of natural resources MX15 has to be the object of a selective collection for the electronic equipments and cannot be scrapped with the normal domestic waste The user thus has the obligation t...

Page 18: ...gment 1 3 relay contact outputs potential free NO or NF based on position of jumpers next to relays DEF RL1 RL2 Connector of first sensor with 2 wires Example of connection between a MX15 central unit...

Page 19: ...0 TWIN type sensors L N T MAINS 230VAC 0 24V Remote acknowledgment 1 2 3 Connector of first sensor with 3 active wires relay contact outputs potential free NO or NF based on position of jumpers next t...

Page 20: ...ring 1 2 3 1 2 3 Example of connection with an EXPLO or TOXIC sensor with 3 active wires L N T MAINS 230VAC 0 24V relay contact outputs potential free NO or NF based on position of jumpers next to rel...

Page 21: ...22...

Page 22: ...23 Ex Ox Tox Gasdetectie Westerdreef 5V 2152 CS Nieuw Vennep Telefoon 0252 620885 E mail info exoxtox n Website www exoxtox nl...

Reviews: