background image

 

10

 

3.2.

 

Power supply and load resistance characteristics  

 

Maximum current available between terminals 2 and 3: 300 mA at 20 V. 
Maximum no load voltage between terminals 2 and 3: 30 V 
Load resistance between terminals 1 and 2: 47 ohms 

 
 

4

4

.

.

 

 

M

M

a

a

r

r

k

k

i

i

n

n

g

g

 

 

OLDHAM Arras 

  

 II (3) G 

OSA 05ATEX0120 

 
 

I

I

V

V

.

.

 

 

C

C

e

e

n

n

t

t

r

r

a

a

l

l

 

 

u

u

n

n

i

i

t

t

 

 

i

i

n

n

s

s

t

t

a

a

l

l

l

l

a

a

t

t

i

i

o

o

n

n

 

 

1

1

.

.

 

 

C

C

e

e

n

n

t

t

r

r

a

a

l

l

 

 

u

u

n

n

i

i

t

t

 

 

m

m

o

o

u

u

n

n

t

t

i

i

n

n

g

g

 

 

Mounting is performed using a DIN rail, positioned so that it provides a 5 cm free area around the 
central unit.  
The MX15 central should be installed in all facilities away from explosive atmosphere, preferably 
in  an  attended  area  (control  centre,  console  room,  control  room,  etc.)  and  in  a  less  humid  (no 
condensation) and temperate environment (see chapters 2.1 and 3) 
 
 

2

2

.

.

 

 

C

C

e

e

n

n

t

t

r

r

a

a

l

l

 

 

u

u

n

n

i

i

t

t

 

 

e

e

l

l

e

e

c

c

t

t

r

r

i

i

c

c

a

a

l

l

 

 

c

c

o

o

n

n

n

n

e

e

c

c

t

t

i

i

o

o

n

n

s

s

 

 

Electrical connections should: 

-

 

be performed by a specialist and while the central unit is off (power supply is shut off) 

-

 

comply with existing regulations (including NF C 15-100) 

-

 

has a minimum section of 1.5 mm² and a maximum section of 2.5 mm

for power supply 

from power system (230VAC) 

 
Check  the  current  nature  and  network  voltage  (the  network  voltage  should  match  the  voltage 
specified on the central unit maker’s plate).  
 
 

2.1.

 

Protective ground 

The central unit must be connected to an operating ground.  The ground terminal (yellow ochre) is 

identified by the following symbol:  

 

Refer to wiring examples at the end of the manual.  

Summary of Contents for MX15

Page 1: ...I IN NS ST TA AL LL LA AT TI IO ON N A AN ND D O OP PE ER RA AT TI IN NG G I IN NS ST TR RU UC CT TI IO ON NS S Ref NPM15GB...

Page 2: ...uired particularly for electrical installation and assembly connections service lines Any modification of the equipment as well as use of unauthorized parts will result in cancellation of any warranty...

Page 3: ...ECIFIC USE C C L L A A U U S S E E S S C C O O N N C C E E R R N N I I N N G G P P R R O O P P E E R R T T Y Y Drawings plans specifications and information included in this document contain confident...

Page 4: ...ly 230 Volts 115VAC on request 11 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 24V as indicated in the wiring examples at the end of the manual 11 2 3 Measuring...

Page 5: ...otentiometers A motherboard including all system components power supply display relays and connectors A front face with tactile keys I I I I T T e e c c h h n n i i c c a a l l s s p p e e c c i i f...

Page 6: ...ammable Display front Type LCD screen 4 digits 7 segments 3 characters 14 icon segments 4 LEDs Description of unit and gas programmable by user in a list 3 characters edited by user Keyboard through t...

Page 7: ...h information provided to external units The site manager where the equipment is installed should take into consideration and comply with the information in the following paragraphs Refer to the provi...

Page 8: ...l unit in configuration 0 at 100 LEL The following curve provides a response to the central unit regarding the measured value and fault processing based on the value of the input current supplied by t...

Page 9: ...n attended area control centre console room control room etc and in a less humid no condensation and temperate environment see chapters 2 1 and 3 2 2 C Ce en nt tr ra al l u un ni it t e el le ec ct t...

Page 10: ...should be wired on the two terminals L orange and N blue as indicated in the wiring examples at the end of manual 2 2 2 Power supply 24 VDC protection through F8 can be connected on terminals 0 and 2...

Page 11: ...e in positive safety negative upon request and potential free REL1 terminals match the relay 1 contacts alarm 1 REL2 terminals match the relay 2 contacts alarm 2 The relay contacts can be used normall...

Page 12: ...replaced with an interrupted line on the display unit To return to the measurement display press one of the two keys or To return to normal operation simultaneously press the and keys 2 2 M Me en nu u...

Page 13: ...larms 1 manual MAN if the gas concentration again becomes lower than the preset alarm threshold this alarm must be acknowledged manually by pressing the acknowledgment key 2 or automatical AUT if the...

Page 14: ...changes the access code for various menus 1000 in standard upon shipment of equipment display the CODE menu and key validate it enter display current code indicate the new code using the and keys vali...

Page 15: ...s concentration is correct by reading the display unit Otherwise adjust the sensitivity using a S potentiometer Disconnect the standard gas cylinder Wait for the return to zero on the display unit Pre...

Page 16: ...intended to be a measure of the accuracy of the instrument Industrial scientific further recommends that a full instrument calibration be performed using a certified concentration s of calibration ga...

Page 17: ...onal use of natural resources MX15 has to be the object of a selective collection for the electronic equipments and cannot be scrapped with the normal domestic waste The user thus has the obligation t...

Page 18: ...gment 1 3 relay contact outputs potential free NO or NF based on position of jumpers next to relays DEF RL1 RL2 Connector of first sensor with 2 wires Example of connection between a MX15 central unit...

Page 19: ...0 TWIN type sensors L N T MAINS 230VAC 0 24V Remote acknowledgment 1 2 3 Connector of first sensor with 3 active wires relay contact outputs potential free NO or NF based on position of jumpers next t...

Page 20: ...ring 1 2 3 1 2 3 Example of connection with an EXPLO or TOXIC sensor with 3 active wires L N T MAINS 230VAC 0 24V relay contact outputs potential free NO or NF based on position of jumpers next to rel...

Page 21: ...22...

Page 22: ...23 Ex Ox Tox Gasdetectie Westerdreef 5V 2152 CS Nieuw Vennep Telefoon 0252 620885 E mail info exoxtox n Website www exoxtox nl...

Reviews: