Select
TANK RECHARGING
and set the gas quantity to be taken out from the external bottle and press
ENTER
The unit carries out the recharging into the internal reservoir, signalizing by intermittent tones the
end of the operation.
3.4.3.3 Load cell test
By selecting LOAD CELL TEST you may test the current accuracy of balance of the gas tank. The unit
displays on the first row the weight of the applied sample weight and, onsecond row, the total value read on
the cell, both in analogic and in digitale form ( botttom)
Press ENTER
1) Relative weight (weight of the sample for test purppose)
2) Currrent weight of the tank
3) Digital value
Hook a smaple weight to the load cell (balance) in order to test the weight measurement
(in order to calibrate the load cell, follow the specific instructions in the service manual)
3.4.3.4 Printing of refrigerant management report
Press ENTER
1) “From” - “To” values
2) Data regarding the gas and oil quantities innthe time period
Select REPORT PRINT to print (if a printer is available on the unit) a report including:
a) total recovered refrigerant quantity (starting from the last counter reset)
b) total recharged refrigerant quantity (starting from the last counter reset)
c) total recharged oil quantity (starting from the last counter reset)
At the end of the print out, the user is required to choose if the counters have to be reset to “0” or not.
Press on ENTER to reset all counters or “EXIT” to maintain the existing data