3) Controller parameters
Battery voltage parameters
Measure the parameters in the condition of 12V/25ºC. Please double the values in the 24V system
and multiplies the values by 4 in the 48V system.
Battery type
Battery parameters
sealed
gel
flooded
USE
over voltage disconnect
voltage
16.0V
16.0V
16.0V
9~17V
charging limit voltage
15.0V
15.0V
15.0V
9~17V
over voltage reconnect
voltage
15.0V
15.0V
15.0V
9~17V
equalize charging voltage
14.6V
--
14.8V
9~17V
boost charging voltage
14.4V
14.2V
14.6V
9~17V
float charging voltage
13.8V
13.8V
13.8V
9~17V
boost reconnect charging
voltage
13.2V
13.2V
13.2V
9~17V
low voltage reconnect
voltage
12.6V
12.6V
12.6V
9~17V
under voltage warning
reconnect voltage
12.2V
12.2V
12.2V
9~17V
under voltage warning
voltage
12.0V
12.0V
12.0V
9~17V
low voltage disconnect
voltage
11.1V
11.1V
11.1V
9~17V
discharging limit voltage
10.6V
10.6V
10.6V
9~17V
equalize duration
120 minutes
--
120 minutes
0
~
180 minutes
boost duration
120 minutes
120 minutes
120 minutes
10
~
180 minutes
When the battery type is "USE," the battery voltage parameters follow the following logic:
A
.
Over Voltage Disconnect Voltage > Charging Limit Voltage
≥
Equalize Charging Voltage
≥
Boost
Charging Voltage
≥
Float Charging Voltage > Boost Reconnect Charging Voltage.
B
.
Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage
C
.
Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage
≥
Discharging Limit Voltage.
D
.
Under Voltage Warning Reconnect Voltage>Under Voltage Warning Voltage
≥
Discharging Limit
Voltage.
E
.
Boost Reconnect Charging Voltage >Low Voltage Reconnect Voltage.