SMART TERMINAL
INSTALLATION & COMMISSIONING
(Yellow)
The LED is illuminated when one or more zone detectors, loop devices or
panel outputs are disabled.
Evacuate
Turns on all alarm devices (visual and aural) outputs and activates the Fire indicator. The SILENCE /
RESOUND or RESET control shall turn off all alarm devices (visual and aural).
Active at access level 2 only
(Green)
Illuminated to show the presence of power. Flashes when mains have
failed.
(Yellow)
Illuminated when the FACP is unable to provide mandatory functions.
LED is latched, until cleared by reset.
(Yellow)
Illuminated when there is an earth fault detected on the panel.
(Yellow)
Illuminated steady if any of the alarm devices (sounders and/or
strobes) have been disabled and flashes if any of the alarm devices (sounders and/or strobes) are in
fault. Disable has priority over fault.
(Yellow)
Illuminated steady if the fire output has been disabled and flashes if
the fire output is in fault (open or short circuit condition). Disable has priority over fault.
(Yellow)
Illuminated when the FACP is in the test mode. Possible tests are
alarm, fault, walk, lamp and loop.
(Red)
Illuminated when a Zone is in alarm