SMART TERMINAL
INSTALLATION & COMMISSIONING
(Red)
The LED is illuminated when one or more devices are reporting a FIRE
condition and are not disabled.
Silence Buzzer
Silences the panel buzzer. Buzzer is activated under the following conditions:
Alarm condition
Devices – missing, out of calibration, wrong type, reporting an internal error
Loops – short circuit or open circuit
Monitored inputs and outputs on loop devices are in fault
Sounders – missing, wrong type or reporting an internal error
Modules within the panel – missing, wrong type or hardware error
Main and secondary power supply fault
In Configuration mode this key decreases the LCD contrast.
Push button – held down for 3 seconds commences a lamp test. Lamp test is to test all indicators,
segments on the LCD and the buzzer.
Active at access level 1 and 2.
(Yellow)
LED is illuminated when there are one or more faults on the system. Faults
can be;
Devices – missing, out of calibration, wrong type, reporting an internal error
Loops – short circuit or open circuit
Monitored inputs and/or outputs on loop devices in fault
Monitored inputs and/or outputs within the FACP in fault
Modules within the panel – missing, wrong type or hardware error
Modules or stations external to the panel – missing, wrong type or hardware error
(
SmartTerminal
)
Main and secondary supplies
Reset
Returns the FACP to its default power up state. This means all detectors in alarm are reset to normal
and all indicators and outputs are updated accordingly.
In Configuration mode this key increases the LCD contrast.
Active at access level 2 only.