17
616 01 1019 00
Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or
larger for normal wiring applications. Continuous wire lengths
over 100 ft. should use 20 AWG or larger.
NOTE
: The communicating bus wiring only requires a
four-wire connection; however, it is good practice to run ther-
mostat cable having more than four wires in the event of a
damaged or broken wire during installation.
Each communicating device in the system has a four-pin
connector. It is recommended that the following color code
be used when wiring each device:
DX+ — Green = Data A
DX- — Yellow = Data B
C — White = 24VAC (Com)
R — Red = 24VAC (Hot)
NOTE:
TERMINAL MARKINGS FOR EACH COMMUNICAT-
ING SYSTEM COMPONENT MAY NOT BE IN THE SAME
ORDER. IT IS NOT MANDATORY THAT THE ABOVE COL-
OR CODE BE USED, BUT EACH CONNECTOR IN THE
SYSTEM
MUST
BE WIRED CONSISTENTLY.
A separate four-pin connector comes inside packaging and
should be used when connecting to furnace (or fan coil). En-
sure connector is inserted properly into circuit board.
1. Turn off all power to equipment.
2. If an existing thermostat or control is being replaced:
a. Remove existing thermostat from wall.
. . . . . . .
b. Disconnect wires from existing thermostat.
. . . . . . .
c. Discard or recycle old thermostat.
. . . . . . .
Summary of Contents for TSTAT0201CW
Page 12: ...12 616 01 1019 00 A14558 2 Press under All Days then press EDIT...
Page 20: ...20 616 01 1019 00 3 90 5 20 0 97 Fig 2 Wall Control Assembly Pieces...
Page 25: ...25 616 01 1019 00...
Page 65: ...65 616 01 1019 00 Zones...
Page 76: ...76 616 01 1019 00...
Page 77: ...77 616 01 1019 00...
Page 78: ...78 616 01 1019 00...