Auto Mode
When Auto Mode is enabled (factory default) a change from
heat to cool (or vice versa) will not occur until the current
cycle is satisfied and an opposite mode demand has existed
for 30 minutes. If the set-point is changed, the 30 minute
timer is deleted.
Enable/Disable Auto Changeover mode (default = En-
able).
Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
Setpoint Deadband
The minimum difference enforced between heating and cool-
ing desired temperatures. This can allow one setting to
“push” the other to maintain this difference.
0 to 6ºF (0 to 3ºC), (default = 2ºF)
Offsets
This option allows calibration (or deliberate mis-calibration)
of the temperature and humidity sensors. These offsets are
added to the actual temperature/humidity values (default =
0).
Temperature Offset: -5ºF to +5ºF (-3ºC to +3ºC)
Outside Temp Offset: -5ºF to +5ºF (-3ºC to +3ºC)
Humidity Offset: -10 to +10%
Cycles Per Hour
Maximum cycles per hour = 4 (default) or 6.