MASTER-SLAVE ALARM INPUT CONNECTION
The smart controller can accept a TLAN communication via the 6-POS connector terminals 5 and 6 marked MS1
and MS2 located on the enclosure side of the unit. This TLAN communication is associated with the controller
display alarm “LC” and “LC1”, lost communication.
To use the TLAN communication feature, simple connect the TLAN harness to MS1 and MS2 terminals and to
MS1 and MS2 of each unit in parallel.
REMOTE ACCESS CONTROL
AIR CONDITIONER UNIT COMMUNICATION FEATURES
An optional communication board offers capabilities that include Profinet, EtherNet/IP, Modbus TCP, and SNMP
protocols through Ethernet and Modbus RTU protocol via USB. Hoffman® Cooling has a PC Interface Tool
available for download that can utilize either mode to communicate with the air conditioner unit.
USB COMMUNICATION
This communication mode allows direct connection of a PC to the air conditioner unit. The protocol
supported is Modbus RTU. Use the PC Interface Tool to communicate with the air conditioner unit. A
MINI-b USB connection is provided.
ETHERNET COMMUNICATION
This communication mode allows remote connection to the air conditioner unit using SNMP, Modbus
TCP, EtherNet/IP, and Profinet protocols. Customers using their own software can download a MIB file for
SNMP, Coil_Register file for Modbus TCP, EDS file or EtherNet_IP Object file for EtherNet/IP, and GSDML
file for Profinet.
NOTE: ACU has a default IP Address of 192.168.1.2
Both Ethernet and USB communication modes allow the ability to:
• Read ACU inlet and outlet air temperatures
• Read and change Cooling Set-point and Cooling Differential
• Read and change Heating Set-point, Heating Differential
• Read and change High and Low Temperature Alarm Settings
• Read and change Gateway IP Address, Device IP Address, Subnet Mask, Trap IP Address and Community
•
Read and change Unit Identification
• Read and change the state of IP addressing (static or dynamic)
• Read current Alarm Status
• Read MAC Address
• Read and change the door open and/or smoke detected switch polarity
SOFTWARE AND CONFIGURATION FILE DOWNLOADS
The PC Interface Tool, MIB file, EDS file, EtherNet_IP Object file and Coil_Register file can be downloaded
MASTE-SLAVE CAPABILITY (OPTIONAL)
In the master-slave application, only one Remote Access Communication board is required. All alarms
are communicated through the TLAN serial connection, except the door open and/or smoke detected
alarm. Door open and/or smoke detected switch polarity can be remotely changed from Normally Open to
Normally Close if needed.
Note that if the door open and/or smoke detected harness is not used, and the door switch is
wired to only one of the units, for instance, the master unit. If the power of the master unit is
OFF, the slave units will NOT detect the door open alarm and they will continue operating in
standalone mode even if the door is open.
SOFTWARE AND CONFIGURATION FILE DOWNLOADS
The PC Interface Tool, MIB file, Coil_Register file, EDS file or EtherNet_IP Object file, and GSDML file can be
downloaded from
http://www.nventprotect.com/en/na/Product-Enclosure-Cooling-Heating