The resulting chart showing the Inlet Air Temperature and the Outlet Air Temperature will appear
as shown above.
To change the Legend for the sensor readings, click on the legend at the right side of the chart,
right click and click on“Select Data”. Then click on “Series 1”, click on “Edit”, enter “Inlet Air” in text
box, and click “OK”. Repeat for “Series 2” and name it “Outlet Air”.
To add a title to the Y-Axis of the chart, click on the chart, click on “Layout”, click on “Axis Titles”,
click on “Primary Vertical Axis Title”, and, finally, click on “Rotated Title”. A text box will appear to
the left of the numbers. Click on the text and change it to “Degrees F”.
If a title on the top of the chart is desired, click on the chart, click on “Layout”, click on “Chart Title”,
click on “Above Chart”. A text box will appear above the chart. Click on the text and change it to
“Compressor 6”.
The above resulting chart had the ACU Cooling Setpoint set to 80F and the Cooling Differential set
to 10F. From this graph, one can see that the corresponding Inlet Temperature varied between 80F
and 90F.