Load Verification (Pump, Blower, etc.): 

If a Load will not turn off: Unplug the 

Keypad. If the load is still on, there is a fault in the Control Box. Replace the 
Control Box. 
 
If a Load will not turn on: Referring to the Operating Instructions section, 
confirm that the Load is plugged into the correct Receptacle of the correct 
Control Box. If it still does not function, verify that the Load is operational by 
plugging it directly into a known-good wall receptacle. If not, replace the 
Control Box or Load accordingly. 
 

Non-Functional Keypad:

 If the Keypad is not functioning, check that the 

control box has power by observing the green power indicator LED on the 
control box is illuminated. 
 
Next, check the cable connecting the Keypad to the control box making sure 
that both connections are secure. Inspect each cable end to make sure that 
the pins are not bent or missing. If the Keypad is still non-functional, replace 
the Keypad and the Cable. Test the system. 
 

Summary of Contents for TOUCHSTONE CSLC-317-02-01-01

Page 1: ...317 02 01 01 Single Load Controller Multi Speed Triac Load Installation Operating Manual with Troubleshooting and Configuration Guide NuWhirl Systems Corp www nuwhirl com 951 817 5600 MANCSLC31702 REV...

Page 2: ...by a Ground Fault Circuit Interrupter GFCI Contact a qualified electrician if you cannot verify that the power supply is protected by a GFCI The GFCI should be tested on a routine basis Consult the G...

Page 3: ...ration P 4 Important Installation Notes Mounting P 6 CSLC 317 02 01 01 Multi Speed Air Blower Triac Model Installation Feature Operations P 8 Operations P 10 System Troubleshooting P 14 All Installati...

Page 4: ...hese are the configurations currently available as of September 22 2021 CSLC 317 02 01 01 Triac Model CAUTION Ensure that the Controller Model is suitable for the Tub s Load that is to be controlled F...

Page 5: ...from the AC power and wait about 10 seconds 3 Plug the control box back in The green Power LED will blink the current configuration that it is in 4 Within 20 seconds press and hold the Configuration B...

Page 6: ...t have a center screw Load This Controller is only compatible with 120 Volt Brush Type Pumps and Brush Type Blowers with a Maximum Rating of 12 Amps Plug the Load into the Receptable at the bottom of...

Page 7: ...overtighten 4 Turn the power back on and confirm correct operation Note If the remaining receptacle above the Controller is being used the total load must not exceed the circuit s rating Additional In...

Page 8: ...12 CICL 297 Tub Lights x2 Max Configs 1 thru 6 Air Switch Option Configs 1 7 thru 12 To 120V GFCI Protected Receptacle 15A or 20A Duplex Female Socket TO PUMP OR BLOWER Max 12A Load CCBL 372 CCBL 366...

Page 9: ...to fully understand and safely utilize the tub System Features Air Buttons Function Timers Variable Speed Pump or Variable Speed Blower Multi Color LED Tub Lights Activation Air Switch Buttons which m...

Page 10: ...its 30 minute timer and activate the Tub Light in a Rainbow mode Subsequent presses will change the color to Blue White Blue Aqua Green Yellow Red Magenta and off The Tub Light will turn off automati...

Page 11: ...the Blower on at high speed and activate its 30 minute timer Subsequent presses will change the speed to medium low oscillate mode and off The system will stop automatically when the timer expires The...

Page 12: ...the speed to medium low oscillate mode and off The system will stop automatically when the timer expires Configuration 8 Variable Speed Pump w Oscillation Option No Light The Whirlpool Water system is...

Page 13: ...the Button a third time turn the Blower off Configuration 12 Variable Speed Blower w Oscillation Option No Light 24 Hour Purge Cycle The Air System is activated by pressing the Air Air Button The Air...

Page 14: ...f these cables were cross connected or forced in at any point irreparable damage may result and any warranty will be void Should this happen replace all the affected components ensuring that they are...

Page 15: ...not function verify that the Load is operational by plugging it directly into a known good wall receptacle If not replace the Control Box or Load accordingly Non Functional Keypad If the Keypad is not...

Page 16: ...tems Corp www nuwhirl com 951 817 5600 MANCSLC31702 REV A 9 27 2021 Retain this manual for future reference For your records and future reference please fill in data below Manufacturer Model Serial Da...

Reviews: