Load Verification (Pump, Blower, etc.):
If a Load will not turn off: Unplug the
Keypad. If the load is still on, there is a fault in the Control Box. Replace the
Control Box.
If a Load will not turn on: Referring to the Operating Instructions section,
confirm that the Load is plugged into the correct Receptacle of the correct
Control Box. If it still does not function, verify that the Load is operational by
plugging it directly into a known-good wall receptacle. If not, replace the
Control Box or Load accordingly.
Non-Functional Keypad:
If the Keypad is not functioning, check that the
control box has power by observing the green power indicator LED on the
control box is illuminated.
Next, check the cable connecting the Keypad to the control box making sure
that both connections are secure. Inspect each cable end to make sure that
the pins are not bent or missing. If the Keypad is still non-functional, replace
the Keypad and the Cable. Test the system.