Chapter 1 - Getting Started
Cooling Fan Module
8
WARNING:
Do not operate the enclosure for extended periods of time (greater
than 5 minutes) with the cooling fan module removed.
Cooling Fan Module
The enclosure has temperature sensors in three different areas, the drive bay, the
RAID Controller, and the power supplies. There are several steps the storage
system performs to prevent component damage due to over temperature
conditions.
If the drive bay area reaches a temperature of 50°C (122°F) an audible alarm will
sound, the front panel Fan Status LED will flash alternately amber then green, and
the monitoring software will post a warning message. These events are interpreted
by the monitoring system and report in the form of notifications giving the user a
warning that a condition is causing the enclosure temperature to exceed the preset
maximum allowable value. An action is required by the user to determine the cause
and take corrective measures. It may be due to a blockage of air flow or a low fan
speed.
If the RAID Controller reaches a temperature of 65°C (149°F) an audible alarm will
sound, the front panel Fan Status LED will flash alternately amber and green, and
the monitoring software will post a warning message. If the temperature on the
RAID Controller continues to rise and reaches 71°C (159°F) the controller will flush
its cache and shutdown. The controller will also spin down the disk drives at this
temperature.
Fan Speed Override Control
Jumpers JP1 (Fan 0)
and JP2 (Fan 1)
4700F.book Page 8 Wednesday, April 6, 2005 11:05 AM
Summary of Contents for NexStor 4700F Series
Page 2: ...4700F book Page 2 Wednesday April 6 2005 11 05 AM...
Page 8: ...Table of Contents iv 4700F book Page iv Wednesday April 6 2005 11 05 AM...
Page 28: ...Chapter 1 Getting Started Audible Alarm 16 4700F book Page 16 Wednesday April 6 2005 11 05 AM...
Page 104: ...Index 92 4700F book Page 92 Wednesday April 6 2005 11 05 AM...
Page 105: ...4700F book Page 93 Wednesday April 6 2005 11 05 AM...