background image

LUMA-NET

804CP / 808CP 

REMOTE CONTROL PANEL

INSTALLATION AND OPERATION GUIDE

Software Revision 3.00, Version C

INTRODUCTION 

The NSI 804CP and 808CP represents a key part of a state of the art, total lighting control system.  Combined
with NSI dimmers and optionally, an NSI memory control console, a totally integrated system is achieved.

The 804CP and 808CP can automatically take control and preset the lighting level of up to 100 dimmer channels.
Control is automatically passed between control panels and the memory control console as desired.  The 804CP
features 4 zone slide controls while the 808CP features 8 zone slide control.  Both units are exceptionally easy to
operate.  Remote lockout capability is also included.  Installation is a snap with the simple 4 wire digital connection
required.

IMPORTANT

Programming differs from other Luma-net panels, please read instructions.

Programming of dimmer channels beyond factory defaults requires computer and software interface
package

Luma-net control panels with software release 3.00 and higher are not directly compatible and will
not operate with older 400CP panels with software prior to release 3.00.  Contact dealer or factory
for modifications if necessary.

NSI dimming systems used with these release 3.00 panels require the following software releases:

2408CD, 2408CR, 2404CD

release 2.30 and above.

DDS 8600/8800/9600/9800

release 1.30 and above. 

*

DDS 6000

release 1.30 and above. 

*

DDS 5300/5500/5600

release 1.30 and above. 

*

*

 Optional interface kit required for these units.

Summary of Contents for 804CP

Page 1: ...easy to operate Remote lockout capability is also included Installation is a snap with the simple 4 wire digital connection required IMPORTANT Programming differs from other Luma net panels please read instructions Programming of dimmer channels beyond factory defaults requires computer and software interface package Luma net control panels with software release 3 00 and higher are not directly co...

Page 2: ... in any standard double gang electrical box while the 808CP will mount in a large three gang box with the 4 screws provided See below paragraph on system turn on before final mounting of panels SYSTEM TURN ON It is very important that the system operation be verified one panel at a time Else an improper connection at one panel would cause the entire system to not operate properly and may be diffic...

Page 3: ... the network Steady on or Slow flashing Network trying to reconfigure bad ID While programming the following actions are normal Quickly flashing Programming mode LOCKOUT Any 804CP and 808CP may be disabled from operation with a remote key switch or other contact closure Several Luma net panels of the same version may be connected to the same contacts in parallel as long as polarity is maintained C...

Page 4: ... 8 full ALL OFF button levels Zone 1 4 1 8 off The installer may reprogram the PRESET and ALL OFF buttons easily without additional equipment Other features such as dimmer channel assignment and fade time require a computer and software Details on programming other features are supplied with the Luma net Software Package Optionally the unit may be ordered preprogrammed from the factory REMOTE CONT...

Page 5: ...ave a unique network ID number If two panels have the same network ID number the entire network will stop functioning Panels need not be in program mode to change network ID number since a dipwitch is used To set Network ID number 1 Locate dipswitch on rear of unit as illustrated below 2 Set the switches as per the chart on the following page Factory Default Setting The 804CP and 808CP are program...

Page 6: ...10111100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78 01110010 79 11110010 80 00001010 81 10001010 82 01001010 83 11001010 84 00101010 85 10101010 86 01101010 87 11101010 88 00011010 89 10011010 90 01011010 91 11011010 92 00111010 93 10111010 94 0111...

Page 7: ...ll zones of this panel to fade to the current settings of the slide controls All zone LEDs will come on and the slide controls will have full control PRESET button This button will cause all dimmer channels assigned to all zones of this panel to fade to the zone setting previously programmed Default is all full on All zone LEDs will go out ALL OFF button This button will cause all dimmer channels ...

Page 8: ...epair or replace at its option defective materials provided you have identified yourself as the original owner of the product to NSI or any authorized NSI dealer Transportation charges to and from an authorized dealer or the NSI factory for repair shall be the responsibility of the owner All products returned to NSI must have factory authorization for return prior to shipping NSI Corporation is no...

Reviews: