WIRING 

The 804CP and 808CP will only operate with NSI dimming and control systems explicitly designed for interfacing
with it.  Communication between the panels and the dimming system is via a 4 wire interface.  Three wires carry
the RS 422/485 bi-directional data.  A fourth wire carries the DC voltage necessary for powering the unit.

Wiring cable between the panels and the dimming system is class 2 and should be at least 22 AWG, 4 conductor
shielded, twisted pairs.  (BELDEN 8302, 8723; 22 AWG.) Use 20 AWG for runs over 500ft.

The 804CP and 808CP may be connected to the dimming system via parallel or daisy-chained wiring.  Due to
power supply current demands, panels must be limited to 5 units per daisy chain run with 22 awg wire, or 10
units with 20 AWG wire.

The Luma-net panels feature plug on wiring terminals.  The terminals may be unplugged from the panel to facilitate
ease of wiring and testing. Connect the terminals marked , remote-, common, and +15 VDC to the same
respective terminals on the dimming system and other Luma-net panels.  Use one twisted pair for and
remote- and the other pair for common and +15 VDC.

The wiring to the remote lockout switch, if used, can be simple 2 conductor 22 AWG.  Connect  the wires from
the switch to the and lockout- terminals.  Any panel or group of panels may be locked-out remotely by
interrupting the +15V supply to the panels.  This should not affect any other panels still powered, or affect lighting
levels currently set.

IMPORTANT: Verify wiring is correct before powering system!  Make sure nothing conductive may touch
pc board or components!

MOUNTING 

The 804CP and will mount in any standard double-gang electrical box, while the 808CP will mount  in a large
three-gang box with the 4 screws provided.   See below paragraph on system turn-on before final mounting of
panels.

SYSTEM TURN-ON

It is very important that the system operation be verified one panel at a time.  Else, an improper connection at
one panel would cause the entire system to not operate properly and may be difficult to diagnose.

After all terminal plugs have been wired and the dimmer system has been installed and tested, the installer is ready
to connect each panel to the system.  Panels may be plugged-in while system is live, but the installer must take
care not to touch PC board or connections with fingers or metal objects.  On daisy-chain runs,  the panels closest
to the dimming system should be connected first.  

804CP and 808CP panels have dip switches to set network ID number and must have their ID programmed before
the system power is connected.   It is recommended that the installer review the programming procedures for
network ID before proceding.

    A duplicate network ID number will cause the entire network to malfunction.

Connect the first panel and  immediately notice whether the POWER LED comes on, indicating power to the
panel.   The BUSY LED  should come on momentarily and then go out and stay out.  This indicates a successful
reconfiguration of the network.  If the BUSY LED flashes slowly, this indicates a duplicate ID number or wiring
problem.  Program the ID number, if not already, and observe the BUSY LED.  (Note, the busy LED also flashes
quickly when the program jumper is removed).

Now test the dimmer function by operating the panel.  If the dimmer responds, then mount the panel and procede
to the next panel in the system and follow the same procedure.

REMOTE CONTROL PANEL
Software Revision 3.00, Version C

NSI CORPORATION

2

Summary of Contents for 804CP

Page 1: ...easy to operate Remote lockout capability is also included Installation is a snap with the simple 4 wire digital connection required IMPORTANT Programming differs from other Luma net panels please read instructions Programming of dimmer channels beyond factory defaults requires computer and software interface package Luma net control panels with software release 3 00 and higher are not directly co...

Page 2: ... in any standard double gang electrical box while the 808CP will mount in a large three gang box with the 4 screws provided See below paragraph on system turn on before final mounting of panels SYSTEM TURN ON It is very important that the system operation be verified one panel at a time Else an improper connection at one panel would cause the entire system to not operate properly and may be diffic...

Page 3: ... the network Steady on or Slow flashing Network trying to reconfigure bad ID While programming the following actions are normal Quickly flashing Programming mode LOCKOUT Any 804CP and 808CP may be disabled from operation with a remote key switch or other contact closure Several Luma net panels of the same version may be connected to the same contacts in parallel as long as polarity is maintained C...

Page 4: ... 8 full ALL OFF button levels Zone 1 4 1 8 off The installer may reprogram the PRESET and ALL OFF buttons easily without additional equipment Other features such as dimmer channel assignment and fade time require a computer and software Details on programming other features are supplied with the Luma net Software Package Optionally the unit may be ordered preprogrammed from the factory REMOTE CONT...

Page 5: ...ave a unique network ID number If two panels have the same network ID number the entire network will stop functioning Panels need not be in program mode to change network ID number since a dipwitch is used To set Network ID number 1 Locate dipswitch on rear of unit as illustrated below 2 Set the switches as per the chart on the following page Factory Default Setting The 804CP and 808CP are program...

Page 6: ...10111100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78 01110010 79 11110010 80 00001010 81 10001010 82 01001010 83 11001010 84 00101010 85 10101010 86 01101010 87 11101010 88 00011010 89 10011010 90 01011010 91 11011010 92 00111010 93 10111010 94 0111...

Page 7: ...ll zones of this panel to fade to the current settings of the slide controls All zone LEDs will come on and the slide controls will have full control PRESET button This button will cause all dimmer channels assigned to all zones of this panel to fade to the zone setting previously programmed Default is all full on All zone LEDs will go out ALL OFF button This button will cause all dimmer channels ...

Page 8: ...epair or replace at its option defective materials provided you have identified yourself as the original owner of the product to NSI or any authorized NSI dealer Transportation charges to and from an authorized dealer or the NSI factory for repair shall be the responsibility of the owner All products returned to NSI must have factory authorization for return prior to shipping NSI Corporation is no...

Reviews: