![Novatech Bitronics M87X Series Manual Download Page 85](http://html1.mh-extra.com/html/novatech/bitronics-m87x-series/bitronics-m87x-series_manual_1711100085.webp)
ML0021 August 15, 2018
69
Copyright 2018 Bitronics, LLC
5.5.1a Introduction to FTP
FTP protocol is a standard component of the Internet protocol suite and is used to transfer
files between computer systems. Every Windows/Unix/Linux operating system contains an
FTP Client program that allows simple access to FTP Servers such as the M87x. FTP is
accessed from the command prompt (sometimes referred to as the DOS prompt). A
(simplified) sample session appears on the screen as:
C:\windows>
FTP 192.168.0.254
M87x server, enter user name:
anonymous
Enter password: BITRONICS (Any password will work)
FTP>
binary
Some Operating Systems default to ASCII mode for FTP. Entering "binary" ensures that
the FTP connection will be in the binary mode necessary for communicating with the
M87x.
As shown above, the user specifies the IP address of the server, enters a username and
password, and then is presented with the FTP prompt awaiting commands. The following
commands are useful for communicating with the M87x.
Command
Function
BINARY
Changes FTP to binary mode
CD..
Change current directory to parent directory
CD directoryname
Change current directory to directyname
DELETE filename.ext
Delete file from Server
DIR filename.ext
List directory contents
GET source file destination file
Read file from M87x
PUT source file destination file
Write file to M87x
QUIT
Exit FTP server and return to command prompt
Refer to your local operating system documentation for more details.
5.5.1b M87x FTP Implementation
The M87x FTP server has three privilege levels that determine the allowed FTP
operations.
Description
Username
Password
Read files within the C:\DATA directory
“anonymous” or “guest”
Any
Read files on any drive or directory
Drive\directory
Level 0
Read, Write, or Delete files on any drive or directory
Drive\directory
Level 2
Access to Levels 1 and 2 require the user to enter the starting (root) directory as the "User
Name". For this purpose, the drive name is treated as a directory. The entire "c" drive
would be accessed by entering a User Name of "c" and the appropriate password. Access
to a subdirectory, for example the configuration files, is obtained by entering a User Name
Summary of Contents for Bitronics M87X Series
Page 2: ......
Page 45: ...ML0021 August 15 2018 29 Copyright 2018 Bitronics LLC...
Page 46: ...ML0021 August 15 2018 30 Copyright 2018 Bitronics LLC Figure 6 Host Port Signal Assignment...
Page 113: ...ML0021 August 15 2018 97 Copyright 2018 Bitronics LLC...
Page 114: ...ML0021 August 15 2018 98 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 115: ...ML0021 August 15 2018 99 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 116: ...ML0021 August 15 2018 100 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 117: ...ML0021 August 15 2018 101 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 118: ...ML0021 August 15 2018 102 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 119: ...ML0021 August 15 2018 103 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 169: ...ML0021 August 15 2018 153 Copyright 2018 Bitronics LLC Figure A 16...
Page 174: ...ML0021 August 15 2018 158 Copyright 2018 Bitronics LLC...
Page 176: ...ML0021 August 15 2018 160 Copyright 2018 Bitronics LLC...
Page 177: ...ML0021 August 15 2018 161 Copyright 2018 Bitronics LLC...
Page 178: ...ML0021 August 15 2018 162 Copyright 2018 Bitronics LLC...
Page 179: ...ML0021 August 15 2018 163 Copyright 2018 Bitronics LLC...
Page 181: ...ML0021 August 15 2018 165 Copyright 2018 Bitronics LLC...
Page 182: ...ML0021 August 15 2018 166 Copyright 2018 Bitronics LLC...
Page 183: ...ML0021 August 15 2018 167 Copyright 2018 Bitronics LLC...