ML0021 August 15, 2018
xiv
Copyright 2018 Bitronics, LLC
Voltage and current connections should be made using insulated crimp terminations to
ensure that terminal block insulation requirements are maintained for safety. To ensure
that wires are correctly terminated, the correct crimp terminal and tool for the wire size
should be used.
Before energizing the equipment, it must be grounded (earthed) using the protective
ground (earth) terminal, or the appropriate termination of the supply plug in the case of
plug connected equipment. Omitting or disconnecting the equipment ground (earth) may
cause a safety hazard.
The recommended minimum ground (earth) wire size is 2.5 mm
2
(#12 AWG), unless
otherwise stated in the technical data section of the product documentation.
Before energizing the equipment, the following should be checked:
1.
Voltage rating and polarity
2.
CT circuit rating and integrity of connections
3.
Protective fuse rating
4.
Integrity of ground (earth) connection (
where applicable
)
5.
Equipment operating conditions
The equipment should be operated within the specified electrical and environmental limits.
Current transformer circuits
Do not open the secondary circuit of a live CT since the high voltage produced may be
lethal to personnel and could damage insulation.
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of
each part of the test, the voltage should be gradually reduced to zero, to discharge
capacitors, before the test leads are disconnected.
Removal and insertion of modules
All M87x active circuitry is located on removable modules. Unless a Module is specifically
intended for Hot Swap (see documentation), it must not be inserted into or withdrawn from
equipment while it is energized, since this may result in damage. Hot Swap modules may
be installed and removed under power. Refer to the appropriate section or manual to
determine if the particular module is Hot Swap compatible.
For all other modules,
remove all power from the unit before installing or removing any module.
All Hazardous Voltages MUST be removed from the M87x before removing or
Summary of Contents for Bitronics M87X Series
Page 2: ......
Page 45: ...ML0021 August 15 2018 29 Copyright 2018 Bitronics LLC...
Page 46: ...ML0021 August 15 2018 30 Copyright 2018 Bitronics LLC Figure 6 Host Port Signal Assignment...
Page 113: ...ML0021 August 15 2018 97 Copyright 2018 Bitronics LLC...
Page 114: ...ML0021 August 15 2018 98 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 115: ...ML0021 August 15 2018 99 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 116: ...ML0021 August 15 2018 100 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 117: ...ML0021 August 15 2018 101 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 118: ...ML0021 August 15 2018 102 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 119: ...ML0021 August 15 2018 103 Copyright 2018 Bitronics LLC Figure 9 Signal Connections M871...
Page 169: ...ML0021 August 15 2018 153 Copyright 2018 Bitronics LLC Figure A 16...
Page 174: ...ML0021 August 15 2018 158 Copyright 2018 Bitronics LLC...
Page 176: ...ML0021 August 15 2018 160 Copyright 2018 Bitronics LLC...
Page 177: ...ML0021 August 15 2018 161 Copyright 2018 Bitronics LLC...
Page 178: ...ML0021 August 15 2018 162 Copyright 2018 Bitronics LLC...
Page 179: ...ML0021 August 15 2018 163 Copyright 2018 Bitronics LLC...
Page 181: ...ML0021 August 15 2018 165 Copyright 2018 Bitronics LLC...
Page 182: ...ML0021 August 15 2018 166 Copyright 2018 Bitronics LLC...
Page 183: ...ML0021 August 15 2018 167 Copyright 2018 Bitronics LLC...