Applications
Connecting an NBG-12LRA Agent Release-Abort Station
b.
Circuits are supervised against opens and shorts.
6.
Refer to the NFS2-3030 Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the
NFS2-3030 Programming Manual.
4.9 Connecting an NBG-12LRA Agent Release-Abort Station
Typical Connections
Figure 4.14 shows typical connections for wiring an NBG-12LRA Agent
Release-Abort Station.
4.10 Connecting an FAAST Intelligent Aspiration Detector
The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection
using aspiration sensing technology.
SLC loop to
FACP’s
LCM-320 or
LEM-320
FCM-1
FRM-1
FMM-101
FMM-101
Black
Red
Yellow
Violet
Black
Red
Yellow
Violet
Non-rese24 VDC from
AMPS-24/E
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369 for
installation details.
ELR mode R-47K
supervised and
power-limited
Red
Brown
24 VDC UL-listed
releasing device
C.
N.O.
3
030-
N
B
G12
L
R
A
tp
H
.w
m
f
System
Common (–)
24 VDC power
from FACP’s
main power supply
N.C.
Figure 4.14 Typical Connections for an NBG-12LRA Agent Release-Abort Station
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.
REL-47K
(use with Type Code
“Rel Ckt ULC”)
NOTE:
See Circuit Requirements for Section 4.7, “Connecting a Releasing Device to FCM-1
Control Modules (Retrofit applications only)”, on page 53.
NOTE:
Devices for use in releasing applications must be programmed as type code RELEASE
CIRCUIT or REL CKT ULC.