52
NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
Applications
Releasing Applications
4.5.9 Security Annunciation
A1P1
Mode: Monitor
Source: ZLc
A1P2
Mode: Monitor
Source: ZLe
A1P3
Mode: Monitor
Source: LXXMYY
A1P4
Mode: Monitor
Source: LXXMYY
Additional doors can be
monitored, up to the number of
available annunciator points.
4.6 Releasing Applications
4.6.1 Overview
This control panel can be used for non-hazardous agent release or preaction/deluge control
applications via the SLC loop. In a properly configured system with compatible, listed actuating
and initiating devices, this control panel complies with the following NFPA standards for
installation in accordance with the acceptable standard:
Refer to installation documents for the individual SLC loop device for voltage and maximum
current requirements.
4.6.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
control modules. Program control module FCM-1 or FCM-1-REL for the appropriate Type Code
according to the chart below:
For more information, refer to the NFS2-3030 Programming Manual.
a
c
m
-2
4atface
.cdr
Figure 4.10 Sample Annunciator Display
System Status
(red is armed)
System Alarm
(red is alarm)
Entry/Exit Door 1 Status
(red is unsecured)
Entry/Exit Door 2 Status
(red is unsecured)
Standard
Covers
NFPA 13
Sprinkler Systems
NFPA 15
Water Spray Systems
NFPA 16
Foam-Water Deluge and Foam-water Spray Systems
NFPA 17
Dry Chemical Extinguishing Systems
NFPA 17A
Wet Chemical Extinguishing Systems
NFPA 2001
Clean Agent Fire Extinguishing Systems
Table 4.1 NFPA Standards for Releasing Applications
Type Code: RELEASE CKT
•
For use in UL applications
•
Do not use REL-47K
•
Cannot use power-limited wiring
•
Supervised for open circuit only
•
Supervised for power loss
Type Code: REL CKT ULC
•
For use in UL or ULC applications
•
Requires REL-47K at solenoid
•
Power-limited wiring
•
Supervised for open circuit and shorts
•
Supervised for power loss