Fire/Security Applications
Applications
Contact Switches with Monitor Modules
Address: LXXMYYY
(arbitrary)
Type ID:
ACCESS MONITOR
Zone Map:
ZA
Custom Label: Exit Door #
Motion Detectors with Monitor Modules
Address: LXXMYYY
(arbitrary)
Type ID:
ACCESS MONITOR
Zone Map:
ZB
Custom Label: Motion Detection
2.
Programming of Logic Equations
Logic Equation for 1 minute exit delay:
ZLa* = DEL(01:00, 00:00, address of key switch)
Logic Equation for Trouble arming system:
ZLb* = AND (ZA, address of key switch, NOT(Zla))
Logic Equation to arm system:
ZLc* = AND (ZLa, NOT(ZLb))
Logic Equation providing 30-second entry delay:
ZLd* = SDEL(00:30, 00:30, ZA)
Logic Equation for Security Alarm:
ZLe* = AND (ZLc, OR (ZLd))
*Follow the following restrictions on values:
a < b < c < d <e
3.
Programming Group Interfaces
Group Interface for Trouble when system is armed while access point(s) active
A. CM programming
Address:
LXXMYYY (arbitrary)
Type ID:
RELAY
Zone Map:
ZLb
Custom Label: Arming Trouble Group Output
Signal Silence: No
Walk Test:
Yes/No (Installer Specified)
Switch Inhibit: Yes
B. MM Programming
Address:
LXXMYYY (arbitrary)
Type ID:
TROUBLE MON
Zone Map:
(none)
Group Interface for Security Alarm
A. CM programming
Address:
LXXMYYY (arbitrary)
Type ID:
RELAY
Zone Map:
ZLe
Custom Label: Security Group Output
Signal Silence: No
Walk Test:
Yes/No (Installer Specified)
Switch Inhibit: Yes
B. MM Programming
Address:
LXXMYYY (arbitrary)
Type ID:
SECURITY-L
Zone Map:
(none)
MM
CM