2. Installation
Annunciator Circuits
32
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Annunciator Circuits
Connectors are provided for Terminal Mode (TB7) and ACS Mode (TB5) annunciators. When
connecting a Terminal Mode annunciator be sure to configure switch SW3 on the main circuit board for
the appropriate device. Note that TB7 Out and In polarities are used for connecting Terminal Mode
annunciators.
Note:
Devices connected to the standard EIA-485 connector, the optional EIA-232/EIA-485 connector may be
protected from voltage transients by using one of the UL-listed compatible surge suppressors listed in the
Notifier
Device Compatibility Document
.
Figure 11 Annunciator Interface
Notification Appliance Circuits
The AFP-100 provides two Notification Appliance Circuits configurable for Style Y or Style Z. Each
circuit is capable of 2.5 amps of current. Total current drawn from these as well as other DC power
outputs cannot exceed 6.0 amps. Use UL-listed 24 VDC notification appliances only. Circuits are
supervised and power-limited. Refer to the
Device Compatibility Document
for a listing of compatible
notification appliances. The two NACs (Notification Appliance Circuits) located on the main circuit
board may be expanded using the FCPS-24(E) Field Charger/Power Supply.
Note:
Surge protection for notification appliances may be provided by using one of the UL-listed compatible surge
suppressors listed in the
Device Compatibility Document
.
Figure 12 NAC Connections
1 COMM 2
ACS
OUT+ IN+ OUT- IN-
T
B
7
T
B
5
EIA-485 connection for ACS
Mode annunciator. Refer to
"UDACT", or appropriate
annunciator manual for
information on wiring.
EIA-485 connection for
Terminal Mode annunciator.
Refer to appropriate
annunciator manual for
information on wiring.
Note:
TB7 is also an EIA-232
connection for a PC/Printer.
92
00A
C
S
T
.cdr
BELL 2 POWER
BELL 1 POWER
B+ A+ A- B-
B+ A+ A- B-
T
B
2
T
B
1
+ –
+ –
+ –
+ –
+ –
+ –
Style Z Notification Appliance Circuit
(supervised and power-limited)
Style Y Notification Appliance Circuit
(supervised and power-limited)
Polarized Bell
Polarized Strobe
Polarized Horn
Dummy Load all
unused circuits
9200-
nac.cdr
4.7K ohm, ½ watt
EOL, PN 71252
(UL-listed)
Notification Appliance
Circuit polarity shown in
alarm state.
Technical Manuals Online! - http://www.tech-man.com