Wiring a Signaling Line Circuit
2. Installation
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
33
Wiring a Signaling Line Circuit
Overview
The AFP-100 communicates with addressable initiating, monitor and control devices through a
Signaling Line Circuit (SLC). You can wire the SLC to meet the following NFPA requirements of
NFPA Style 4, Style 6 or Style 7.
Device Capacity
The capacity of the AFP-100 includes up to 99 addressable detectors and an additional combination of
up to 99 addressable pull stations, control modules, and monitor modules. In addition, the control panel
supports two NACs.
Surge Suppression
Surge protection for the SLC may be provided by using one of the UL-listed compatible surge
suppressors listed in the
Notifier Device Compatibility Document
. The SLC is allowed to leave the
building only with the use of a UL-listed surge suppressor found in the Notifier Device Compatibility
Document.
Installation
For installation information see the
SLC Wiring Manual
.