Program Change – Level One
3. Programming
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
47
To load the addressable device's program into memory at any time, press the
ENTER
key. After pressing
the
ENTER
key, autoprogram displays the next new detector. If a detector was previously entered into
memory, but is missing (no answer), the LCD display shows the following:
If the
ENTER
key is pressed, the device is deleted from memory and autoprogram displays the next new
device. If the left arrow is pressed, the program is unchanged and the next new device is displayed.
After all new detectors are presented for editing, the autoprogram feature displays the modules on the
SLC starting with the device found at the lowest address.
Monitor Modules
This program is similar to the New Detector Autoprogram. When a new monitor module is presented, a
typical display might be:
The major program editing for monitor modules is the selection of the Type Code on the first line. To
change this selection, use the up and down arrow keys as the entire field blinks. The default selection is
monitor as shown in the screen above. Note that selection of a Type Code
may change the functional
operation of the addressable device as shown below.
Table 5 Monitor Module Type Codes
Follow the same procedure as described in New Detectors section, for editing of the ADJ and NOUN
fields. The default zone selection is Z00 (main circuit board NAC outputs 1 and 2) and may be set to
Z01 through Z56 if desired. See "Appendix C: Software Zones" on page 80.
The ADJ field for monitor modules can also be used to associate a second zone as described in "New
Detectors" on page 45.
Type Code Label
Special Function
MONITOR
none (default)
PULL
BOX
none
HEAT
DET
none
SMOKE
ZON
none
WATERFLOW
causes a nonsilenceable alarm
SUPERVISY
becomes supervisory point (see Section 4,
Operation)
AUTO
SUPV
becomes supervisory point
(nonlatching
supervisory)
TAMPLER
_
SW
becomes supervisory point (see Section 4,
Operation)
_________
none (blank label for use when no other
Type Code applies)
ACK
_
SW
___
functions like the
ACKNOWLEDGE
switch
SILENC
SW
functions like the
SILENCE
switch
RESET
SW
functions like the
RESET
switch
DRILL
___
functions like the
DRILL
switch
PROGRA SMOKE DET P01
NO ANSWER DELETE
PROGRM MONITOR M01
<ADJ> <NOUN> Z00
Technical Manuals Online! - http://www.tech-man.com