Terminals, Connectors & Switches
1. Product Description
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
13
Terminals, Connectors & Switches
The figure below shows the terminals, connectors and switches that are located on the AFP-100 main
circuit board.
Figure 2 AFP-100 Main Circuit Board
24V UNREG 24V NONRS 24V RST
BELL 2 POWER
BELL 1 POWER
SUPV
ALARM
TROUBLE
PC/PRINTER TERM COMM
G
N
D F
A
UL
T
DI
SABL
E
TR
A
N
S
F
O
R
M
E
R
1
TR
AN
SF
O
R
M
E
R 2
- +
BATTERY
RS
-2
3
2
PC
/P
R
INT
ER
R
S
-485
TE
R
M
. M
O
D
E
TR
O
U
B
LE
+ - + - + -
B+ A+ A- B-
B+ A+ A- B-
NO C NO NC C NO NC C
A B B+ A+ B- A-
1 COMM 2
ACS
SHIELD
SLC
SLC
OUT+ IN+ OUT- IN-
T
B
4
T
B
2
T
B
1
T
B
3
T
B
7
T
B
5
T
B
6
J16
J6
JP3
JP1
CAUTION
HIGH VOLTAGE
J3
TB8
J19
J17
JP4
SW1
SW3
SW2
C
AUTIO
N
!
HI
G
H
V
O
L
TAG
E
GNDFAULT
TB4
- 24 VDC Power
TB1
- NAC Circuit 1
TB2
- NAC Circuit 2
TB6
- SLC
TB5
- ACS COMM
TB7
TERM COMM
PC/PRINTER
TB3
- Relays
TROUBLE
ALARM
SUPV
TB8
- AC
EARTH
NEUTRAL
HOT
JP1
- Battery Charger
Disable
Cut to disable FACP
battery charger when
using external charger
J3
- Battery Connector
JP3
- Ground Fault Disable
Cut to disable Ground Fault
Detection Circuit
SW3
- EIA-232/EIA-485 Selection
Up position selects EIA-232 for PC/Printer
connection.
Down position selects EIA-485 for
Annunciator connection
SW2
- Trouble
Normal position is up for no AC fail
reporting delay.
If using UDACT for Central Station,
SW2 must be down, as shown, to
enable AC Loss Delay reporting.
J6
- Connector for
optional RTM-8F
Module
JP4
- RTM-8F Supervision
Cut jumper to supervise RTM-8F
module when installed
SW1
- Write Protect
Up position is write protect.
Down position, as shown, is
nonwrite protect which
allows panel programming.
Ground Fault LED
J16
-
UDACT
Connector
J17
Xformer 1
High
Voltage
J19
Optional
Xformer 2
High
Voltage
9200b
ord.cd
r