Troubleshooting
Electrical Control System
141
2.4.4.12. P3 malfunction
P3 display
Current protection of compressor
The protection occurred in
standby
Yes
Yes
Measure whether the
current is normal
?
Yes
No
Replace the outdoor main PCB
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal
?
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage
of bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of
L and N well or
correctly
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
No
No
Yes
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer
to
the
Appendix
3
?
Replace the bridge
rectifier
No
Check whether
bridge rectifier is
normal
Check the wiring of
reactor or inductance
Reconnect the
wiring
No
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Replace outdoor main
board
No
No
Check if the outdoor fan
runs properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Yes
Yes
Check whether system pressure
is too high
Recycle the over charged
refrigerant
Yes
Summary of Contents for MOC-12HFN1-MS0W
Page 2: ......
Page 4: ......
Page 19: ...Service Space Indoor Units 15 4 Service Space ...
Page 21: ...Wiring Diagrams Indoor Units 17 MCD 24HRFN1 M MCD 36HRFN1 M MCD 48HRFN1 M MCD 24HRFN1 MW ...
Page 33: ...Wiring Diagrams Indoor Units 29 MTB 24HRFN1 MW ...
Page 34: ...Wiring Diagrams 30 Indoor Units MTB 24HRFN1 M MTB 36HWFN1 M MTB 48HWFN1 M ...
Page 48: ...Service Space 44 Indoor Units 3 Service Space 12K 18K C 35mm 35mm 35mm 1000mm 24K 48K ...
Page 50: ...Wiring Diagrams 46 Indoor Units MUE 24HRFN1 M MUE 36HRFN1 M MUE 48HRFN1 M ...
Page 57: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 58: ...Service Space 54 Indoor Units 3 Service Space ...
Page 59: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 63: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 70: ...Wiring Diagrams 66 Outdoor Units 4 Wiring Diagrams MOC 12HFN1 MV0W ...
Page 71: ...Wiring Diagrams Outdoor Units 67 MOZ 12HFN1 MW0W ...
Page 72: ...Wiring Diagrams 68 Outdoor Units MOC 12HFN1 MS0W MOF 18HFN1 MS0W MOF 18HFN1 MU0W ...
Page 73: ...Wiring Diagrams Outdoor Units 69 MOU 24HFN1 M ...
Page 74: ...Wiring Diagrams 70 Outdoor Units MOG 24HFN1 MT0W ...
Page 75: ...Wiring Diagrams Outdoor Units 71 MOU 36HFN1 M MOU 48HFN1 M ...
Page 100: ...Indoor unit installation 96 Installation ...
Page 138: ...Troubleshooting 134 Electrical Control System 2 4 4 5 E3 malfunction ...
Page 143: ...Troubleshooting Electrical Control System 139 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 149: ...Troubleshooting Electrical Control System 145 2 4 4 16 P7 malfunction ...