Electrical Control Function
118
Electrical Control System
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at auto speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at auto speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off
1.3.7.4 Shutdown, change the mode or speed setting will cancel the economic operation.
1.3.7.5 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the timing is
less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing is more than 7
hours, the machine will not stop until reaches the setting time in sleep mode.
For other units:
1.3.7.1 The economy function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including swing function) automatically after 3 minutes
when power returns.
1.3.9 Drain pump control (For cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling), dehumidifying, and forced cooling mode, the
pump will start running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes,
1.3.10 Point Check Function (Excluding 12K &18K units &MOG-24HFN1-MT0W)
There is a check switch in outdoor PCB.
Summary of Contents for MOC-12HFN1-MS0W
Page 2: ......
Page 4: ......
Page 19: ...Service Space Indoor Units 15 4 Service Space ...
Page 21: ...Wiring Diagrams Indoor Units 17 MCD 24HRFN1 M MCD 36HRFN1 M MCD 48HRFN1 M MCD 24HRFN1 MW ...
Page 33: ...Wiring Diagrams Indoor Units 29 MTB 24HRFN1 MW ...
Page 34: ...Wiring Diagrams 30 Indoor Units MTB 24HRFN1 M MTB 36HWFN1 M MTB 48HWFN1 M ...
Page 48: ...Service Space 44 Indoor Units 3 Service Space 12K 18K C 35mm 35mm 35mm 1000mm 24K 48K ...
Page 50: ...Wiring Diagrams 46 Indoor Units MUE 24HRFN1 M MUE 36HRFN1 M MUE 48HRFN1 M ...
Page 57: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 58: ...Service Space 54 Indoor Units 3 Service Space ...
Page 59: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 63: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 70: ...Wiring Diagrams 66 Outdoor Units 4 Wiring Diagrams MOC 12HFN1 MV0W ...
Page 71: ...Wiring Diagrams Outdoor Units 67 MOZ 12HFN1 MW0W ...
Page 72: ...Wiring Diagrams 68 Outdoor Units MOC 12HFN1 MS0W MOF 18HFN1 MS0W MOF 18HFN1 MU0W ...
Page 73: ...Wiring Diagrams Outdoor Units 69 MOU 24HFN1 M ...
Page 74: ...Wiring Diagrams 70 Outdoor Units MOG 24HFN1 MT0W ...
Page 75: ...Wiring Diagrams Outdoor Units 71 MOU 36HFN1 M MOU 48HFN1 M ...
Page 100: ...Indoor unit installation 96 Installation ...
Page 138: ...Troubleshooting 134 Electrical Control System 2 4 4 5 E3 malfunction ...
Page 143: ...Troubleshooting Electrical Control System 139 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 149: ...Troubleshooting Electrical Control System 145 2 4 4 16 P7 malfunction ...