Drainage pipe installation
Installation
101
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
Summary of Contents for MOC-12HFN1-MS0W
Page 2: ......
Page 4: ......
Page 19: ...Service Space Indoor Units 15 4 Service Space ...
Page 21: ...Wiring Diagrams Indoor Units 17 MCD 24HRFN1 M MCD 36HRFN1 M MCD 48HRFN1 M MCD 24HRFN1 MW ...
Page 33: ...Wiring Diagrams Indoor Units 29 MTB 24HRFN1 MW ...
Page 34: ...Wiring Diagrams 30 Indoor Units MTB 24HRFN1 M MTB 36HWFN1 M MTB 48HWFN1 M ...
Page 48: ...Service Space 44 Indoor Units 3 Service Space 12K 18K C 35mm 35mm 35mm 1000mm 24K 48K ...
Page 50: ...Wiring Diagrams 46 Indoor Units MUE 24HRFN1 M MUE 36HRFN1 M MUE 48HRFN1 M ...
Page 57: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 58: ...Service Space 54 Indoor Units 3 Service Space ...
Page 59: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 63: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Page 70: ...Wiring Diagrams 66 Outdoor Units 4 Wiring Diagrams MOC 12HFN1 MV0W ...
Page 71: ...Wiring Diagrams Outdoor Units 67 MOZ 12HFN1 MW0W ...
Page 72: ...Wiring Diagrams 68 Outdoor Units MOC 12HFN1 MS0W MOF 18HFN1 MS0W MOF 18HFN1 MU0W ...
Page 73: ...Wiring Diagrams Outdoor Units 69 MOU 24HFN1 M ...
Page 74: ...Wiring Diagrams 70 Outdoor Units MOG 24HFN1 MT0W ...
Page 75: ...Wiring Diagrams Outdoor Units 71 MOU 36HFN1 M MOU 48HFN1 M ...
Page 100: ...Indoor unit installation 96 Installation ...
Page 138: ...Troubleshooting 134 Electrical Control System 2 4 4 5 E3 malfunction ...
Page 143: ...Troubleshooting Electrical Control System 139 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 149: ...Troubleshooting Electrical Control System 145 2 4 4 16 P7 malfunction ...