24
S
ECTION
6
Communication Settings –
used for radio
communication setup.
Drop Out Time –
the machine will go into
default mode if radio communication is lost for
more than the speci
fi
ed time.
Auto Restart Functions –
used to restart the
program upon the primary unit’s return from a
communication loss or power loss.
Communication Regain –
in the event of
communication being restored, the program
will auto restart (if enabled).
Dead Battery State –
when the batteries reach
23.0 V, the unit will enter default operation.
Normal operation will be restored once the
batteries reach the low battery state of 23.6 V
or greater.
Blackout –
when the batteries reach 21.0 V, the
lamps go dark but the GUI is still operational.
Normal operation will be restored once the
batteries reach the low battery state of 23.6 V
or greater.
Set New Passcode –
user selectable passcode
used to unlock the software settings (see S
ECTION
5.3 S
YSTEM
P
ASSCODE
).
Date & Time –
the date and time can be set by
using the up and down arrow buttons to select
the value and the right and left arrow buttons to
toggle horizontally.
Software Import/Export –
software updates and
preprogrammed traf
fi
c plans can be imported via
fl
ash drive. Exporting can be used to save plans.
This will save all settings to the USB
fl
ash drive.
Level of Operation –
two types of methods to
setup a unit; Basic and Advanced.
Basic –
quick, easy setup using prede
fi
ned
layouts (see S
ECTION
7 S
ETTING
U
P
A
W
ORK
Z
ONE
).
Advanced –
ring and barrier based traf
fi
c
control. The advanced mode will change the UI
slightly (see S
ECTION
8 A
DVANCED
M
ODE
).
COMPATIBILTY
WITH
FEB/01/17 09:53AM
PROGRAM: MODEL V##
HOME >
OPTIONS PG 3
BATTERY:
24.0 VOLTS
UNIT:
PRIMARY
RADIO CHANNEL:
03
RADIO SIGNAL:
DEFAULT FLASH RED
PRESS START TO RESUME
UNIT OF
MEASURE
LEVEL OF
OPERATION
GATE ARM
INTRUSION
ALARM
PREV
PAGE
LOCK
SOFTWARE
GEN 3
BASIC
FEET
NEXT
PAGE
Compatibility With –
allows the Gen 3 system
to operate with older Gen 1 or 2 controllers.
If compatibility with an older Gen controller is
selected, some programming options within the
Gen 3 software will be inaccessible (grayed out)
in order to comply with the older versions (see
S
ECTION
9 C
OMPATIBILTY
M
ODE
).
Note: When operating in Gen 1 or 2 compatibility
mode, the Gen 3 system must ALWAYS be the
PRIMARY unit. The Gen 1 or 2 units shall all be
set as SECONDARY units.
Auxiliary Equipment
AWF Units –
timing inputs to control the on/
off
fl
ash times of Advanced Warning Flashers
(AWF).
DAD Change Interval –
enable/disable the
way in which the Driveway Assistance Device(s)
(DAD) transition from displaying a
fl
ashing
arrow to the solid red indication. ENABLE allows
the
fl
ashing arrow to transition to a solid arrow
display for the duration of the yellow change
interval before proceeding to the solid red
indication.
Factory Settings –
gives you the option to
enable or disable display dimming and TFR
hardware.
Display Dimming –
When enabled, if no
button on the controller is pressed for 10
minutes, the screen will go black. Press any
button to illuminate the screen.
Transfer Flasher Relay (TFR) Hardware –
the
TFR is used for transferring control of the local
signal indications in the event of a fault.
Note:
Disabling the TFR requires wiring changes.
Contact NAT before altering this setting.
Set Model –
Manufacturer access only. Contact
NAT for further details.
Motor Control –
This feature enables or
disables the operation sequence of the light
post lift systems by means of the controller
DATE & TIME
FEB/01/17 09:53AM
PROGRAM: MODEL V##
HOME >
OPTIONS PG 2
BATTERY:
24.0 VOLTS
UNIT:
PRIMARY
RADIO CHANNEL:
03
RADIO SIGNAL:
DEFAULT FLASH RED
PRESS START TO RESUME
COMMUNICATION
SETTINGS
SET NEW
PASSCODE
AUTO-RESTART
FUNCTIONS
SOFTWARE
IMPORT/EXPORT
NEXT
PAGE
PREV
PAGE
LOCK
SOFTWARE