 DTI installation

 

     Page 21 of 66

 

DTI/CPI

Installation and data administration

 

Figure 8
N/NT, 51, RT, and 61 single and half group cabling arrangement

QCAD130 to PRI or NT8D79xx 

to QPC720 PRI 

(Secondary Reference)

QPC471

Clock

 Controller

 1

J3

J1

J2

QPC471

Clock

 Controller

 0

J3

J1

J2

QCAD130 to PRI

or NT8D79xx

QCAD125 or

NT8D75xx

J1

QPC720 PRI 

(Primary Reference)

Network

Card

J6

RS232

J4

T1

J3

LOOP

REF1

QCAD130 to PRI

or NT8D79xx

QCAD128

or

QCAD133

or

NT8D83xx

22 AWG ABAM

Cabinet

I/O Panel

Cabinet

I/O Panel

QCAD133

to PRI or

NT8D79xx

QCAD129

or

NT9J93xx

RS232 or

NT8D89Ax

T1

LD-1

Note 2

Central 

Office

J2

REF2

QCAD124 or

NT8D85xx

DS-1

Cross-Connect

J5

(Connector J5 is not used in the DTI application)

T1 interface to 
external digital  
carrier

AAAA

A

A

A

AAAAA

Echo Canceller

RS232

Note 1

T1

A

A

A

AAAA

A

A

AAAAA

Note 1:    Maximum cable distance from  DTI circuit packs to DS-1 cross-connect  is 655 ft.
Note 2:    Maximum cable distance from DTI circuit packs to LD-1 is 750 ft.
Note 3:   Connections below the dotted line are used only with an Echo Canceller.
Note 4:   QPC720 does not interface with NT8D04 Superloop Network Card.

553-1336

Note 3

Summary of Contents for QPC471

Page 1: ...1991 1994 All rights reserved Printed in the United States of America Information is subject to change without notice Northern Telecom reserves the right to make changes in design or components as pr...

Page 2: ...ision bars are omitted December 31 1992 Standard release 3 0 This document is issued to include technical updates Changes are noted with revision bars in the margins August 1 1993 Standard release 4 0...

Page 3: ...0 Installation procedures 11 Removing the DTI card 15 ST STE systems 15 MS systems 18 N NT and RT systems 20 XN XT systems 24 21A 21 51 61 71 and 81 26 Echo Canceller interface 27 Clock Controller ins...

Page 4: ...I DTI to Clock Controller cable 41 Data administration 43 DTI data administration 44 CPI data administration 51 Acceptance tests 53 Self test procedures 53 Automatic loop test 54 Automatic loop test p...

Page 5: ...ings in DTI mode 17 Figure 5 Switch settings in DTI mode 18 Figure 6 MS cabling arrangement 19 Figure 7 Switch settings in DTI mode 20 Figure 8 N NT 51 RT and 61 single and half group cabling arrangem...

Page 6: ...TI 7 Table 4 SW3 options for the QPC720 PRI DTI 8 Table 5 QPC720 PRI external connectors 8 Table 6 DTI cables and cable lengths 10 Table 7 Possible card locations by system 11 Table 8 Cable connection...

Page 7: ...for QPC471 vintage A 29 Table 14 Clock Controller switch settings for QPC471 vintages B C D E F and G 30 Table 15 Clock Controller switch settings for QPC471 vintage H 31 Table 16 Clock Controller sw...

Page 8: ...nd later for ST systems Release 12 and later for RT systems Release 15 and later for system options 21 21A 51 61 and 71 Release 18 and later for system options 21E STE and 81 Note Throughout this docu...

Page 9: ...mation Meridian 1 system installation procedures 553 3001 210 Circuit card installation and testing 553 3001 211 ISDN Primary Rate Interface installation 553 2901 200 Digital Trunk Interface Computer...

Page 10: ...Rate Interface PRI card Because this document deals with DTI functions both cards are referred to as the DTI card or DTI hardware whenever their function is identical Clock Controllers synchronize th...

Page 11: ...example the NTQRY551 Channel Service Unit installed at each connection point of a private system to a registered common carrier trunk Echo Cancellers are required only if satellite transmission is use...

Page 12: ...gure 1 illustrates the faceplate layout Table 1 QPC472 transmission equalization SW2 switch settings for DTI Switch S2 settings To repeatered facility To cross connect point 5 ON 0 45 m 0 150 ft 0 15...

Page 13: ...ctive J3 Q P C 4 7 2 J1 J2 J4 J5 FLR ACT R ALM Y ALM LP BK To T1 trunk To Echo Canceller port Loopback test PRI or NT8D79xx to QPC720 PRI secondary reference J1 J2 PRI or NT8D79xx to QPC720 PRI primar...

Page 14: ...olts at 50 milliamperes The QPC720 PRI contains five LEDs and six external connectors Table 3 shows the transmission equalization SW2 switch settings and Table 4 shows SW3 options Table 5 lists the ex...

Page 15: ...OFF except as shown under the column labeled Switch S2 settings The switch positions of the 8 pole SW3 location E37 are OFF for DTI mode For PRI mode set SW3 positions as configured in LD 17 Note 2 F...

Page 16: ...An access point to the regenerated DS 1 signal from the external network An access point to the DS 1 signal being transmitted by the DTI assembly XMT MON Buffered recovered clocks derived from the ex...

Page 17: ...T1 transmission cable consult the Northern Telecom Transmission Division To manufacture cables of different lengths than the standard cables provided see Wire list on page 57 Table 6 lists the types o...

Page 18: ...Table 7 Possible card locations by system System Shelf Module Slot ST STE CE DTI expansion 5 12 2 8 MS CE CE expansion 5 12 2 9 11 12 12 13 N NT RT Network LH Network RH DTI expansion RT only 5 12 2 1...

Page 19: ...condary reference clock source QCAD130 NT8D79xx QPC720 J2 QPC471 CC 1 J2 Only when primary clock source For RT in Single Group mode only not for ST STE or MS QCAD130 NT8D79xx QPC720 J2 QPC471 CC 1 J1...

Page 20: ...l Run via cabinet I O panel to cross connect terminal or Echo Canceller from shielded system QCAD133 NT8D83xx QPC720 QPC472 J4 J5 Patch panel Run via cabinet I O panel to cross connect terminal or Ech...

Page 21: ...n show cabling arrangements for the QPC720 card The equivalent connections on the DTI card are as follows 8 If required install connecting blocks at MDF or wall mounted cross connect terminal 9 If req...

Page 22: ...t Echo Canceller and at carrier interface for example Office Repeater NCTE equipment 6 Tag and disconnect cables from card Rearrange Clock Controller card cables if required 7 Remove DTI and Network c...

Page 23: ...ller Note 4 QPC720 does not interface with NT8D04 Superloop Network Card QCAD130 to PRI or NT8D79xx QCAD130 to PRI or NT8D79xx to QPC720 PRI Secondary Reference QPC471 Clock Controller 0 J3 J1 J2 QCAD...

Page 24: ...DTI CPI Installation and data administration Figure 4 Switch settings in DTI mode QPC720 PRI DTI SW2 7 pole SW3 8 pole QPC472 DTI SW1 8 pole use 1 7 553 1335 Note See tables on switch settings for PRI...

Page 25: ...en no vacant positions are available to install DTI cards additional Network shelves can replace Peripheral Equipment shelves located on the rear of the Common Equipment Tape or Disk shelves If an add...

Page 26: ...eller Note 4 QPC720 does not interface with NT8D04 Superloop Network Card QCAD130 to PRI or NT8D79xx QCAD130 to PRI or NT8D79xx to QPC720 PRI Secondary Reference QPC471 Clock Controller 0 J3 J1 J2 QCA...

Page 27: ...eripheral Equipment shelves located on the rear of the Common Equipment Tape or Disk shelves Refer to Installing an additional Network shelf on the N NT on page 22 for details If an additional cabinet...

Page 28: ...ABAM Cabinet I O Panel Cabinet I O Panel QCAD133 to PRI or NT8D79xx QCAD129 or NT9J93xx RS232 or NT8D89Ax T1 LD 1 Note 2 Central Office J2 REF2 QCAD124 or NT8D85xx DS 1 Cross Connect J5 Connector J5 i...

Page 29: ...ear PE shelf if required 4 Install the additional Network shelf in the PE location See Step 3 5 Install a QUD15 cooling unit directly below the Network shelf and secure with four mounting screws 6 Ins...

Page 30: ...e C11 Otherwise the procedure is identical 12 At the QCAD111 power wiring harness untie and then connect the C17 connectorized power connection cable to the right rear Network shelf connect the C19 co...

Page 31: ...itional Network shelves can replace Peripheral Equipment shelves located on the rear of the Common Equipment Tape or Disk shelves If an additional cabinet is required to install more Network shelves u...

Page 32: ...Cross Connect J5 Connector J5 is not used in the DTI application T1 interface to external digital carrier AAAA A A A AAAAAAA Echo Canceller RS232 Note 1 T1 AA AA AA AA AA AAAA A A A AAAAAA QPC471 Clo...

Page 33: ...angements refer to Figure 11 Figure 11 DTI to Echo Canceller cabling J4 QPC720 PRI I O Filter Cross Connect Block Echo Canceller NCTE if reqd Network XTIP XRING GRD Shield RTIP RRING GRD Shield If equ...

Page 34: ...he Echo Canceller pin assignments operating parameters and initialization procedures Table 9 DTI to Echo Canceller pin assignments Signal EIA RS232 C circuit designation DTI pin Echo Canceller pin Tra...

Page 35: ...serting the card and connecting the cables Refer to Cable requirements on page 10 for general cabling information This step may also entail removing an old card The remaining sections of this chapter...

Page 36: ...nd 16 below The first three tables display the settings for different vintages of the QPC471 Table 16 shows the settings for the QPC775 Table 12 Clock Controller shelves and slots System Shelf Slot s...

Page 37: ...B C D E F and G System Switch Setting ST STE 21 21A 21E SW1 SW2 Jumper Plug J1 Jumper Plug J2 ON OFF TP8 9 TP11 TP12 MS SW1 SW2 Jumper Plug J1 Jumper Plug J2 ON ON TP9 TP10 TP12 TP13 N NT RT 51 61 SW1...

Page 38: ...the J3 faceplate connectors 0 4 3 m 0 14 ft off off 4 6 6 1m 15 50 ft off on 6 4 10 1m 21 33 ft on off 10 4 15 2 m 34 50 ft on on If there is only one Clock Controller card in the system set to OFF If...

Page 39: ...elf slot and switch setting information Remember not to use both the QPC471 and the QPC775 on a single system QPC471 vintage H cards cannot be mixed with cards of an earlier vintage Starting the Clock...

Page 40: ...DIS CC x Disable system Clock Controller x DSCK loop Disable clock for specified loop DSYL loop Disable yellow alarm processing for loop ENCK loop Enable clock for specified loop ENL CC x Enable syste...

Page 41: ...ounters are near the maintenance or out of service thresholds Excessive switching could generate threshold exceeded messages or cause the PRI to be automatically disabled Check the counters in LD 60 I...

Page 42: ...ENL DIS switch to ENL enable 7 Set the error detection thresholds and clock synchronization control in LD 73 optional if replacing card required with a new installation 8 Enable the Clock Controller b...

Page 43: ...intenance or out of service thresholds Excessive switching could generate threshold exceeded messages or cause the PRI to be automatically disabled Check the counters in LD 60 If necessary reset the c...

Page 44: ...Enable the Clock Controller by entering ENL CC x in LD 60 9 Set the error detection thresholds and clock synchronization controls in LD 73 optional if replacing card required with new installation 10...

Page 45: ...enance or out of service thresholds Excessive switching could generate threshold exceeded messages or cause the PRI to be automatically disabled Check the counters in LD 60 If necessary reset the coun...

Page 46: ...ontrols in LD 73 optional with card replacement required with new installation 9 To track on a Primary or Secondary reference clock use LD 60 The command follows 10 Issue the status check command SSCK...

Page 47: ...condary reference clock source With dual controllers cable QCAD125 NT8D75xx connects the Clock Controller cards to each other at J3 in single group mode NT8D74 Clock Controller to InterGroup cable Thi...

Page 48: ...ration NT8D79 PRI DTI to Clock Controller cable This cable connects the PRI DTI card to the QPC471 Clock Controller card It is available in the following lengths NT8D79AB 0 6 m 2 ft NT8D79AC 1 2 m 4 f...

Page 49: ...s familiar with the general principles of data administration on the Meridian 1 as described in X11 software management 553 3001 300 DTI has an impact on the following Service Change and Print program...

Page 50: ...ise defaults to previous value PREF 0 159 Primary reference source for clock synchronization controller Use cr for free running mode SREF 0 159 Secondary reference source for clock synchronization con...

Page 51: ...Note Automatic restoration is available only with Release 12 and later software See Digital Trunk Interface Computer to PBX Interface maintenance 553 2811 500 for a description SRIM 1 127 Improvement...

Page 52: ...FDL The Yellow Alarm Pattern DG2 Digit 2 FDL Facility Data Link The default is FDL if the frame format is ESF otherwise the default is DG2 TRSH 0 15 Digital Trunk threshold telephone Enter the thresh...

Page 53: ...and 71 R14 For all other machine types TKTP aaa Trunk route type COT FEX WAT DID TIE Central Office trunk route Foreign Exchange trunk route Wide Area Trunk route Direct Inward Dialing trunk route TI...

Page 54: ...must be NO if response to DSEL was VOD SIGO aaa ESN signaling arrangement Prompted if the network signaling package is equipped voice channels are configured VOD and response to TKTP was TIE The allo...

Page 55: ...hannel move to an unassigned channel on the same Network loop RTMB 0 127 1 254 Route number cannot be 31 member number ATDN xxxx Auto terminate DN at which the trunk is to automatically terminate If r...

Page 56: ...OV PAIR NEW OUT Modify existing data Copy a telephone template to add 1 32 new telephones Exit LD 11 Move from one TN to another Move voice and data TNs Add new data to the system Remove data block TY...

Page 57: ...th a direct connection set all maintenance thresholds to their least sensitive values Note 1 If CPI uses a carrier facility requiring an NCTE or Clock Controller follow the DTI instructions for NCTEs...

Page 58: ...l Trunk loop options lll network loop number 0 159 dd number of data calls 0 24 ff frame format D2 D3 D4 or ESF The default for frame format ff is ESF if prompt MODE is set to PRI D3 if MODE is set to...

Page 59: ...ted Self test procedures Follow the steps below to activate the initial test procedure 1 Log into the overlay area 2 Enter LD 60 3 Enter STAT L to receive a status of the DTI card for Loop L 4 Enter D...

Page 60: ...TLP command set to 0 only one channel is tested The channel tested is randomly selected by software and it cannot be specified Automatic loop test procedures Activate automatic loop test procedures wi...

Page 61: ...DTI link from the Meridian 1 to the far end The far end must be in loopback mode before this test can be performed The DTI channel or frame being tested must be disabled before performing the remote l...

Page 62: ...l and the collocated DTIs 6 If the system response is not appropriate refer to Digital Trunk Interface Computer to PBX Interface maintenance 553 2811 500 to analyze the message 7 On the collocated Mer...

Page 63: ...ission Division The following pages contain lists and descriptions applying to Digital Trunk Interface DTI cables external to the Meridian 1 cabinet QCAD129 NT9J93xx This cable is used to connect the...

Page 64: ...mber 1994 Table 17 QCAD129 NT9J93xx wire list DTI signal From To Echo Canceller signal DCD P1 1 P2 20 DTR RXD P1 2 P2 2 TXD DTR P1 4 P2 8 DCD TXD P1 5 P2 3 RXD GND P1 10 P2 7 GND RTS P1 12 P2 4 CTS P1...

Page 65: ...ble 18 contains the wire list for the QCAD133 NT8D97xx Standard length 50 ft 15 3 m Construction Individually foil shielded twisted pairs 24 AWG 0 511 mm stranded P1 Connector 15 pin female subminiatu...

Page 66: ...r ribbon 28 AWG 0 321 mm stranded P1 Connector 15 pin male subminiature D with jack screws P2 Connector 15 pin male subminiature D with jack screws Table 19 QCAD128 NT8D83xx wire list From To Signal P...

Page 67: ...uant to Part 15 of the FCC rules and the radio interference regulations of Industry Canada These limits are designed to provide reasonable protection against harmful interference when the equipment is...

Reviews: