background image

15

while maintaining the full nitrogen flow rate into the liquid 

line. Continue to blast the full nitrogen flow until the sand 

or dirt is removed from the tubing.

 

notE:

 If the dry nitrogen purge is not successful in removing 

the debris, flush the tubing with one to two (depending on 

severity of debris) full large bottles of RX-11. This is done by 

attaching the RX-11 bottle to the liquid line of the sub-surface 

refrigerant tubing, turning the RX-11 bottle upside down, 

and opening the valve all the way. Let the entire bottle flow 

through the sub-surface tubing. Use only approved RX-11 

recovery procedures when evacuating the refrigerant.

6. Remove the temporary valves and reconnect the liquid and 

vapor lines.

7. Evacuate and weigh in the correct initial charge listed in 

Table 4, (page 9)

.

8. Continuously operate the system in the cooling mode for 

at least one full hour, so that any remaining debris will be 

washed up with the liquid refrigerant. If there is more than 

a 3° F differential, install a new filter/dryer in the liquid line 

assembly as often as necessary until there is less than a 

3° F differential.

9. Operate the system in 24 hour segments, changing the filter/

dryer as often as necessary until there is no more than a 

3° F differential across the filter/dryer.

 

notE:

 The filter/dryer may be changed by isolating the 

air handler segment using the shut-off valves inside the 

compressor unit.

operating pressures are too high or too low

(above 375 psig on the High pressure Side and 
80 psig or less on the Low Pressure (Suction) 
Side)

•  During heating to cooling transition, the system pressure 

may initially drop below 80 psig but should rise back to 

correct operational levels. This event is normal for this 

system. During cooling to heating transition, the discharge 

pressure may initially rise above 375 psig but should drop 

back to correct operational levels.

•  Check the filter/dryer in the liquid line assembly. Verify there 

is no more than a 3° F temperature differential. See filter/

drier section on 

page 12

.

•  Check the pressures across the oil separator to determine 

if the filter within the oil separator is dislodged or clogged.

•  Check charge level as detailed in the Starting In Heating 

Mode & Charging To Sight Glass section (page 10).

the system Doesn’t supply Warmed air In the 
Winter or cooled air In the summer

•  Check  system  operational  pressures  for  a  potential 

refrigerant leak (operational pressures will be too low).

 

notE:

 If pressures are too high in the summer, or too low 

in the winter, the geothermal heat pump exchange field 

may have been overstressed. This can be accomplished 

by either turning the system off (use your supplemental 

back-up heating during the winter), for only one 24 hour 

period, or by adjusting the thermostat setting to a higher 

than normal setting during the summer and to a lower than 

normal setting during the winter (usually for several days).

•  When pressures return to normal levels, field return refrigerant 

temperature returns to normal operational temperatures, air 

supply temperatures return to normal levels, and extended 

system operational times return to normal, the field has 

recovered and the temperature settings may be returned 

to their preferred levels.

the compressor unit Will not start

•  Check the time delay on the control board (in the electrical 

box) inside the compressor unit. 

the unit will not start 

until the set time delay period (5 minutes) has expired

after an electrical outage, after a breaker is turned back on, 

after switching from heating to cooling or vice versa, etc.

•  The time delay period may not have expired, or the control 

board may be malfunctioning.

•  Some air handlers may have an internal start delay that will 

effectively prevent total system operation until the delay 

time has expired.

the system Will not Maintain the thermostat 
set Point

•  Check the system charge, head and suction pressures, and 

air handler entering/exiting air temperature differentials. For 

additional charging instructions, see 

page 8

.

•  Check for restrictions in the airflow. Are filters dirty and/or 

is the air return blocked by furniture? Check the thermostat 

also.

•  Check the emergency back-up heat for proper functioning 

if the exterior weather is below design temperatures.

•  Check the return air ducts for leaks and make sure the air 

handler ductwork is tightly sealed. An improperly sealed 

air handler in an unconditioned area will directly pull in 

unconditioned air and overstress the system.

the supply temperature Is too cold

Below 90° F In Heating Mode

•  The  system  has  been  over-stressed  beyond  design 

parameters.

•  The system has been undersized.

•  The CFM and/or the fan setting for the interior air handler 

is too high. 

notE:

 This is a very common occurrence, as 

the fan speed may have been set on high.

Summary of Contents for Y1SA

Page 1: ...ty warnings and any other special notes highlighted in the manual Improper installation of this unit or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require licensed installation service personnel for this type of equip...

Page 2: ...R 410A Charging Procedure 10 Initial Charge 10 Starting In Heating Mode Charging To Sight Glass 10 System Check 11 Air Circulation Indoor Blower 11 System Heating 11 OperatinG Sequence 11 Cooling 11 Heating 11 Unit MAINTENANCE 12 Filter Drier 12 Replacing the Oil Separator Filter 12 Adding Compressor Oil 12 Troubleshooting 13 Two Digit Display 13 Loss Of Capacity 14 Restricted Refrigerant System 1...

Page 3: ...akeitnecessaryfor evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed installation service personnel to service this type of equipment Under no circumstances should the equipment owner attempt to install and or service this equipment Failure to comply with this warning could result in equipment damag...

Page 4: ...d requirement Load estimates can be made using approved methods available from Air Conditioning Contractors of America ManualJ AmericanSocietyofHeating Refrigerating and Air Conditioning Engineers or other approved engineering methods Thisunitisdesignedforindoorandoutdoorinstallationsand shouldbelocatedwithconsiderationgiventotheaccessibility of fuel electric power service access noise shade and d...

Page 5: ...sor section is equipped with components and control logics described in the following sections Heating To Cooling Transition The compressor section includes a hot gas injection valve to ensure smooth transition from heating to cooling mode operations See Figure 6 page 16 After heating mode operation the earth loop temperature maybebelowthenormalundergroundtemperature around 58 F As the refrigerant...

Page 6: ...ler Insulating Interior Line Sets Insulate all interior refrigerant lines and their connections The compressor section contains the expansion valve and the liquid line is more likely to sweat as it condenses moisture from the interior air Use at least a 3 4 inch wall closed cell insulation that is non corrosive to copper to insulate all refrigerant lines Use Armaflex Neoprene or Rubatex having at ...

Page 7: ...rature rather than operating on a preferred temperature maintain mode If the system has electric strip heat back up within the air handler the system can operate together with the electric supplement heat as the strip heating coils are installed downstream of the refrigerant heat exchanger The electric strip heat is supplemental to the heat provided by the geothermal system The thermostat used wit...

Page 8: ...efrigerantlineconnectionsarecompleted itisrequired that you leak check and evacuate the indoor section and all line connections using proper methods before finalizing the full system refrigerant charge For final charges based on matched systems and specified line lengths see Table 4 page 9 Pressure test the entire system at 400 psig with dry nitrogen prior to pulling a vacuum and charging Prior to...

Page 9: ...n by using the following formula TROV ft 3 Total refrigerant charge lb x 40 The examples below were calculated assuming 25 single line length between well and compressor sections L1 and 6 single line length between compressor section and air handler L2 For the 2 ton example the well length is 200 ft and for the 5 ton example the well length is 400 ft as shown in Table 4 Theinstalledsystemiswithane...

Page 10: ...g the compressor to draw high watts Too little refrigerant will freeze the indoor coil in cooling mode operation The recommended charging method is to charge refrigerant to the middle of the sight glass of the accumulator during heating operation In cooling mode with correct R 410A charge the refrigerant returning from the well is in a saturated condition The conventional method of charging by sub...

Page 11: ...rt e If the system has run in the previous 5 minutes a 5 minute anti short cycle timer must expire before the system will restart 3 If the above conditions are met the compressor will start and the reversing valve shift into position if not already in the cooling position a At any time during compressor operation the system will stop if The discharge pressure exceeds 635 psig The suction pressure ...

Page 12: ...lter which is installed at the factory The second filter is to be used as a replacement within 24 to 48 hours of operation These coalescent filters will pick up all dirt and particulates down to 0 3 microns Typical filter driers only catch 50 microns or larger Frequently check the pressure drop across the separator on new installations See Figure 2 and Table 5 page 10 Changethefilterafteraninitial...

Page 13: ...e numbers represent the firmware version When the unit is ready to run it will display which indicates that the unit is in standby mode The display will alternate between the current status and any current or recent events See Table 7 page 14 for status and event codes The display alternates between showing the current status code and the 5 most recent event codes as shown in Table 3 If an event c...

Page 14: ... compressor will eventually overheat and shut off by its own internal overload since the motor s windings are not being cooled by refrigerant vapor Sand Or Dirt In The Sub Surface Tubing Prior to Initial Charging The following steps should be performed if debris removal is required after the field lines have been connected to the liquid line assembly 1 Recoverallrefrigerantfromfromthelinesettotheb...

Page 15: ...d Air In The Winter Or Cooled Air In The Summer Check system operational pressures for a potential refrigerant leak operational pressures will be too low NOTE If pressures are too high in the summer or too low in the winter the geothermal heat pump exchange field may have been overstressed This can be accomplished by either turning the system off use your supplemental back up heating during the wi...

Page 16: ...l Separator Bracket Check Valve Hot Gas Bypass Valve Coil Large Valve Small Valve EXV Valve Coil Solenoid Valve Coil Figure 6 Components H W L 8 72 11 25 13 86 16 38 19 90 22 40 1 54 5 42 5 26 Liquid Line to Air Handler Vapor Line to Air Handler Vapor Line to Earth Loop Liquid Line to Earth Loop Line Voltage Connections Low Voltage Connections Figure 5 Dimensions ...

Page 17: ...nnect to 24 vac 60va class 2 circuit See air handler installation instructions for control circuit and optional relay transformer kits 711415B Replaces 711415A 04 20 W2 W1 O C Y2 R Y1 RELAY THESE WIRES RELAY AND WELL SEAL VALVE ON 4 5 TON 14 17 5 kW UNITS ONLY CCH SUCTION TEMP TO 1PH POWER SUPPLY GND CONTACTOR T2 L2 T1 REVERSING VALVE 1 2 3 4 5 6 7 HOT GAS INJECTOR EXV MOTOR SUCTION PRESSURE SENSO...

Page 18: ...MMN36K B B6EMMN60K C B6EMMN60K C Physical Data Length L 25 1 25 1 25 1 25 1 Width W 25 2 25 2 25 2 25 2 Height H 30 5 30 5 30 5 30 5 Weight 165 170 215 220 Refrigerant Vapor Line O D Both to air handler and earth loop 3 4 3 4 7 8 7 8 Liquid Line O D Both to air handler and earth loop 1 2 1 2 1 2 1 2 Unit is shipped from factory with nitrogen holding charge Table 9 Electrical Physical Data Insulate...

Page 19: ... Star Wade Hampton Nome Yukon Koyukuk North Slope NOTE Zone 1 includes Hawaii Guam Puerto Rico and the Virgin Islands Figure 9 Climate Map IECC Zones Earth Loop Size ft ton 1 2 3A 3B 100 3C 4A 4B 80 4C 5 6 7 8 65 There are exceptions to the earth loop sizes shown in this table Within a climate zone the weather and underground conditions vary from place to place The earth loop length may need to be...

Page 20: ...e size Number of borehole s or Earth Loop s _____________________ Depth of each borehole or Earth Loop____________________ Ft Line set size Vapor line O D Inches _______ Liquid line O D inches ________ Line set distances to each well______________________ distance between the compressor and the air handler Distance feet ___________________________________ Tubing size Vapor line O D Inches _______ ...

Reviews: