14

loss of capacity

•  If  the  system  looses  capacity  (does  not  maintain  the 

thermostat temperature setting), either the system is under-

sized, there is a malfunctioning metering device, or there is 

a possible refrigerant leak. 

notE: 

If a leak occurs, head and 

suction pressures will be low, ice will likely form on the air 

handler refrigerant lines (when the system is in the cooling 

mode), and the compressor will become very hot (usually 

over 200° F in the heating mode).

•  If a leak has occurred, remove all refrigerant, fix the leak, 

and re-weigh in the correct originally recorded amount of 

virgin refrigerant shown in the charging instructions.

•  If the system is under-sized, the problem will typically become 

apparent in cooling mode. As more sub-surface heat transfer 

tubing area exposure is required in the cooling mode than 

in the heating mode. If only modestly under-sized, normal 

supply/return temperature differentials will be close, but not 

at peak, and pressures will be abnormally high during the 

day, but will typically return to close to normal levels by the 

morning.

restricted refrigerant system

The following conditions are apparent in the cooling mode of 

operation. A restriction may not be evident in both the heating 

and the cooling modes of operation.While restrictions may 

result from a number of causes, the following are examples 

of common restrictions.
•  Dirty filter/dryer

•  A crimped/damaged refrigerant line.

•  A mal-functioning reversing valve or expansion device.

•  Debris lodged within an expansion device.

•  Clogged oil separator filter
Check for crimped/damaged refrigerant lines and check the 

metering device. A partial restriction at the metering device 

can result in gurgling sounds, whereas a complete restriction 

will result in no sound at all because there is no refrigerant 

flow. If there is a restriction at the metering device, frost/icing 

may appear on the exterior of the suction line between the 

metering device and the compressor.
If there is a complete restriction, the compressor’s amperage 

draw may be lower than normal since the compressor is running 

in a vacuum with no load. The compressor will eventually 

overheat and shut off by its own internal overload, since the 

motor’s windings are not being cooled by refrigerant vapor.

sand or Dirt In the sub-surface tubing

(Prior to Initial Charging)

The following steps should be performed if debris removal 

is required after the field lines have been connected to the 

liquid line assembly:

1. Recover all refrigerant from from the line set to the borehole.

2. Close off the lower two shut-off valves to the borehole at 

the end of the liquid line assembly.

3. Cut open the vapor lines outside the compressor section.

4. Install a shutoff valve on the top open end of the vapor line. 

notE:

 After the valve is installed, make sure it is in the 

closed position.

5. Starting with a full large bottle of dry nitrogen, fill the line 

set with 500 psig of dry nitrogen, and keep the pressure 

regulator open at 500 psig. Keeping a safe clearance from 

the end of the vapor line, point the end of the vapor line 

away from any object that could be damaged by exiting 

debris. Instantly open the shut-off valve on the vapor line, 

Figure 4. Example of Event code

b

.

p

.

DIsPlaY

DuratIon

(sEconDs)

InDIcatEs

SL

2

Current Status

..

1



2

Most Recent Event

..

1



2

Next Event

..

1



2

Next Event

..

1



2

Next Event

..

1



2

Oldest Event

..

1

Repeats

In this example, the unit has entered soft lock mode due to excessive hot 
gas injection events.

table 8. Example sequence

table 7. status & Event codes

status

coDE

DEscrIPtIon



Unit is running in cooling mode



Unit is running in heating mode



Unit is in standby, waiting for a call to operate

SL

Unit has entered a Soft Lock state due to excessive faults.

EVENT

coDE

DEscrIPtIon



The unit is delaying start because the anti-short cycle timer 

has not yet expired



The unit has opened the Hot Gas Injection Valve



The unit did not start due to high discharge pressure



The unit has stopped due to high discharge pressure



The unit did not start due to low suction pressure



The unit has stopped due to low suction pressure



The suction pressure sensor has a fault



The suction temperature sensor has a fault



The discharge pressure sensor has a fault



The unit has stopped due to excessive Hot Gas Injection 

Events



The unit ended heating mode early due to high suction 

pressure



The unit ended heating mode early due to high discharge 

pressure

Summary of Contents for Y1SA

Page 1: ...ty warnings and any other special notes highlighted in the manual Improper installation of this unit or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require licensed installation service personnel for this type of equip...

Page 2: ...R 410A Charging Procedure 10 Initial Charge 10 Starting In Heating Mode Charging To Sight Glass 10 System Check 11 Air Circulation Indoor Blower 11 System Heating 11 OperatinG Sequence 11 Cooling 11 Heating 11 Unit MAINTENANCE 12 Filter Drier 12 Replacing the Oil Separator Filter 12 Adding Compressor Oil 12 Troubleshooting 13 Two Digit Display 13 Loss Of Capacity 14 Restricted Refrigerant System 1...

Page 3: ...akeitnecessaryfor evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed installation service personnel to service this type of equipment Under no circumstances should the equipment owner attempt to install and or service this equipment Failure to comply with this warning could result in equipment damag...

Page 4: ...d requirement Load estimates can be made using approved methods available from Air Conditioning Contractors of America ManualJ AmericanSocietyofHeating Refrigerating and Air Conditioning Engineers or other approved engineering methods Thisunitisdesignedforindoorandoutdoorinstallationsand shouldbelocatedwithconsiderationgiventotheaccessibility of fuel electric power service access noise shade and d...

Page 5: ...sor section is equipped with components and control logics described in the following sections Heating To Cooling Transition The compressor section includes a hot gas injection valve to ensure smooth transition from heating to cooling mode operations See Figure 6 page 16 After heating mode operation the earth loop temperature maybebelowthenormalundergroundtemperature around 58 F As the refrigerant...

Page 6: ...ler Insulating Interior Line Sets Insulate all interior refrigerant lines and their connections The compressor section contains the expansion valve and the liquid line is more likely to sweat as it condenses moisture from the interior air Use at least a 3 4 inch wall closed cell insulation that is non corrosive to copper to insulate all refrigerant lines Use Armaflex Neoprene or Rubatex having at ...

Page 7: ...rature rather than operating on a preferred temperature maintain mode If the system has electric strip heat back up within the air handler the system can operate together with the electric supplement heat as the strip heating coils are installed downstream of the refrigerant heat exchanger The electric strip heat is supplemental to the heat provided by the geothermal system The thermostat used wit...

Page 8: ...efrigerantlineconnectionsarecompleted itisrequired that you leak check and evacuate the indoor section and all line connections using proper methods before finalizing the full system refrigerant charge For final charges based on matched systems and specified line lengths see Table 4 page 9 Pressure test the entire system at 400 psig with dry nitrogen prior to pulling a vacuum and charging Prior to...

Page 9: ...n by using the following formula TROV ft 3 Total refrigerant charge lb x 40 The examples below were calculated assuming 25 single line length between well and compressor sections L1 and 6 single line length between compressor section and air handler L2 For the 2 ton example the well length is 200 ft and for the 5 ton example the well length is 400 ft as shown in Table 4 Theinstalledsystemiswithane...

Page 10: ...g the compressor to draw high watts Too little refrigerant will freeze the indoor coil in cooling mode operation The recommended charging method is to charge refrigerant to the middle of the sight glass of the accumulator during heating operation In cooling mode with correct R 410A charge the refrigerant returning from the well is in a saturated condition The conventional method of charging by sub...

Page 11: ...rt e If the system has run in the previous 5 minutes a 5 minute anti short cycle timer must expire before the system will restart 3 If the above conditions are met the compressor will start and the reversing valve shift into position if not already in the cooling position a At any time during compressor operation the system will stop if The discharge pressure exceeds 635 psig The suction pressure ...

Page 12: ...lter which is installed at the factory The second filter is to be used as a replacement within 24 to 48 hours of operation These coalescent filters will pick up all dirt and particulates down to 0 3 microns Typical filter driers only catch 50 microns or larger Frequently check the pressure drop across the separator on new installations See Figure 2 and Table 5 page 10 Changethefilterafteraninitial...

Page 13: ...e numbers represent the firmware version When the unit is ready to run it will display which indicates that the unit is in standby mode The display will alternate between the current status and any current or recent events See Table 7 page 14 for status and event codes The display alternates between showing the current status code and the 5 most recent event codes as shown in Table 3 If an event c...

Page 14: ... compressor will eventually overheat and shut off by its own internal overload since the motor s windings are not being cooled by refrigerant vapor Sand Or Dirt In The Sub Surface Tubing Prior to Initial Charging The following steps should be performed if debris removal is required after the field lines have been connected to the liquid line assembly 1 Recoverallrefrigerantfromfromthelinesettotheb...

Page 15: ...d Air In The Winter Or Cooled Air In The Summer Check system operational pressures for a potential refrigerant leak operational pressures will be too low NOTE If pressures are too high in the summer or too low in the winter the geothermal heat pump exchange field may have been overstressed This can be accomplished by either turning the system off use your supplemental back up heating during the wi...

Page 16: ...l Separator Bracket Check Valve Hot Gas Bypass Valve Coil Large Valve Small Valve EXV Valve Coil Solenoid Valve Coil Figure 6 Components H W L 8 72 11 25 13 86 16 38 19 90 22 40 1 54 5 42 5 26 Liquid Line to Air Handler Vapor Line to Air Handler Vapor Line to Earth Loop Liquid Line to Earth Loop Line Voltage Connections Low Voltage Connections Figure 5 Dimensions ...

Page 17: ...nnect to 24 vac 60va class 2 circuit See air handler installation instructions for control circuit and optional relay transformer kits 711415B Replaces 711415A 04 20 W2 W1 O C Y2 R Y1 RELAY THESE WIRES RELAY AND WELL SEAL VALVE ON 4 5 TON 14 17 5 kW UNITS ONLY CCH SUCTION TEMP TO 1PH POWER SUPPLY GND CONTACTOR T2 L2 T1 REVERSING VALVE 1 2 3 4 5 6 7 HOT GAS INJECTOR EXV MOTOR SUCTION PRESSURE SENSO...

Page 18: ...MMN36K B B6EMMN60K C B6EMMN60K C Physical Data Length L 25 1 25 1 25 1 25 1 Width W 25 2 25 2 25 2 25 2 Height H 30 5 30 5 30 5 30 5 Weight 165 170 215 220 Refrigerant Vapor Line O D Both to air handler and earth loop 3 4 3 4 7 8 7 8 Liquid Line O D Both to air handler and earth loop 1 2 1 2 1 2 1 2 Unit is shipped from factory with nitrogen holding charge Table 9 Electrical Physical Data Insulate...

Page 19: ... Star Wade Hampton Nome Yukon Koyukuk North Slope NOTE Zone 1 includes Hawaii Guam Puerto Rico and the Virgin Islands Figure 9 Climate Map IECC Zones Earth Loop Size ft ton 1 2 3A 3B 100 3C 4A 4B 80 4C 5 6 7 8 65 There are exceptions to the earth loop sizes shown in this table Within a climate zone the weather and underground conditions vary from place to place The earth loop length may need to be...

Page 20: ...e size Number of borehole s or Earth Loop s _____________________ Depth of each borehole or Earth Loop____________________ Ft Line set size Vapor line O D Inches _______ Liquid line O D inches ________ Line set distances to each well______________________ distance between the compressor and the air handler Distance feet ___________________________________ Tubing size Vapor line O D Inches _______ ...

Reviews: