background image

6

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed 

at the factory and does not require lubrication.

reFrigerant charging

 Warning:

S6BF Split System air conditioners are shipped 

charged with r410a refrigerant and ready 

for installation. if repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

After refrigerant line connections are completed, it is 

required that you leak check and evacuate the indoor 

section and all line connections (using proper methods) 

before finalizing the full system refrigerant charge.
•  Refrigerant  charging  charts  are  applicable  only  to 

matched assemblies of NORDYNE equipment and listed 

airflows for the indoor coil. Refer to 

Figure 2

Figure 3

Figure 4

Figure 5

, & 

Figure 6

 (

pages  7

8

, & 

9

) for correct system charging.

•  S6BF outdoor units with non-AHRI listed indoor coils 

are not recommended. Deviations from rated airflows or 

non-listed combinations may require modification to the 

expansion device and refrigerant charging procedures 

for proper and efficient system operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the outdoor 

unit. Use only gage line sets which have a “Schrader” 

depression device present to actuate the valve.

charging the unit in ac mode

(With outdoor temperatures above 65° F)
1. With the system operating at steady-state, measure 

the liquid refrigerant pressure (in psig) at the outdoor 
unit service valve.

2. Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure from 

the appropriate charging chart (

Figure 2

Figure 3

Figure 

4

Figure 5

, & 

Figure 6

).

•  If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined 

in Step 3, then there is too much charge in the 

system. Remove refrigerant and repeat Steps 1 

through 3 until the system is correctly charged.

•  If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 

Step 3, there is too little charge in the system. Add 

refrigerant and repeat Steps 1 through 3 until the 
system is correctly charged.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and 
verify the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 
and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds occur, 
determine the source of the noise and correct as 
necessary.

3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes 

and then set the temperature selector above room 
temperature. Verify the fan and compressor cycle off 
with the thermostat. 

note: The blower should also 

stop unless fan mode is set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or 

electric heat) and indoor blower energize. Feel the air 
being circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.

air conditioner maintenance

 Warning:

to prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

 caution:

the unit should never be operated without a 

filter in the return air system. replace disposable 

filters with the same type and size.

Summary of Contents for S6BF-024 Series

Page 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Page 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Page 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Page 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Page 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Page 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Page 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Page 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Reviews: