background image

7

•  This  equipment’s  cooling  system  contains 

refrigerant under high pressure. always use safe 

and environmentally sound methods when handling 

refrigerant handling or servicing the unit. review 

the factory literature and safety warnings prior to 

servicing.

•  When repairing system leaks, always use a nitrogen 

(inert) gas to protect the refrigerant system and pressure 

check the repair before re-charging. Always replace 

the filter-dryers when performing any repair to the 

refrigeration system with one capable of acid removal. 

After completing the repairs, evacuate the system to 

350 - 500 microns and weigh in the refrigerant to the 

amount specified on the unit rating label.

•  The refrigerant charging charts are valid for a variety of 

indoor, return air conditions and are most influenced by 

the outdoor ambient temperature, outdoor fan operation 

and the unit operating voltage.

Figure 2. charging chart for 2 ton units

S6BF-024K Series (txV matches)

200

220

240

260

280

300

320

340

360

380

400

420

440

460

480

500

520

540

560

580

600

75

80

85

90

95

100

105

110

115

120

125

130

135

Liquid Pressure 

(psig)

Liquid Temperature (F)

S6BF-024K Charging Chart -  Cooling

Add refrigerant when below curve

Remove refrigerant when above curve

Figure 2

  Before using these charts, make sure the unit is in a 

stable operating mode. As shown in 

Figure 2

Figure 

3

Figure 4

Figure 5

, & 

Figure 6

, the ideal system sub-

cooling can vary over the range of operation. Reference 

the charts to determine the ideal amount of sub-cooling 

for a given liquid pressure. Units charged to other values 

will not perform at the rated unit efficiency (EER) or rated 

Coefficient of Performance (COP) in heating mode.

•  To inspect a systems operation using quality instruments, 

match the measured liquid temperature to the units 

table. The measured liquid pressure reading should be 

within 3% of the table value for most installations.

•  For systems that are operating with more than a 5% 

deviation, inspect the unit for the proper voltage and 

phase balance and the refrigeration system for leaks.

•  Units that are operating at less then 95% of the nominal 

voltage or with a 2% phase imbalance may see a more 

significant deviation than the amount stated above.

• 

do not use the charts in systems that have a fan cycling 

under low-ambient control. Refer to the low-ambient kit 

instructions for more information (If applicable).

application notes for using charging charts

Summary of Contents for S6BF-024 Series

Page 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Page 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Page 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Page 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Page 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Page 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Page 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Page 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Reviews: