Split SyStem air conditioner

inStallation inStructionS

*S4Be / *Sa4Be - 018, 024, 030, 036, 042, 048, & 060 (1.5, 2, 2.5, 3, 3.5, 4, & 5 ton) SerieS

14 Seer, Single phaSe modelS

important

attention inStallerS:

it is your responsibility to know this product 
better than your customer. this includes being 
able to install the product according to strict 
safety guidelines and instructing the customer 
on how to operate and maintain the equipment 
for the life of the product. Safety should 
always be the deciding factor when installing 
this product and using common sense plays 
an important role as well. pay attention to 
all safety warnings and any other special 
notes highlighted in the manual. improper 
installation of the furnace or failure to follow 
safety warnings could result in serious injury, 
death, or property damage.
these instructions are primarily intended to 
assist qualified individuals experienced in the 
proper installation of this appliance. Some 
local codes require licensed installation/
service personnel for this type of equipment. 
please read all instructions carefully before 
starting the installation. return these 
instructions to the customer’s package for 
future reference.

do not deStroy. pleaSe read careFully & 

Keep in a SaFe place For Future reFerence.

important SaFety inFormation ..............2
air conditioner inStallation .................3

General Information ...........................................3

Before You Install this Unit .................................3

Locating the Air Conditioner ..............................3

Packaging Removal ...........................................3

Ground Level......................................................3

Roof Mount ........................................................3

Connecting Refrigerant Tubing Between the

Indoor & Outdoor Unit ........................................4

electrical Wiring ........................................4

Pre-Electrical Checklist ......................................4

Line Voltage .......................................................4

Grounding ..........................................................5

CoreSense

TM

 Diagnostics Module......................5

Compressor Protection ....................................5

Resetting Alert Codes ......................................5

Thermostat Connections ....................................6

Start up & adJuStmentS ...........................6

Pre-Start Check List ...........................................6

Start-Up Procedures ..........................................6

Air Circulation - Indoor Blower .........................6

System Cooling ................................................6

System Heating (optional) ................................6

air conditioner maintenance .................7
reFrigerant charging ..............................7

Charging the Unit in AC mode ...........................7

Application Notes for Using the Charging Chart 8

Figure 3. Charging Chart for 2 - 5 Ton Units ....8

electrical inFormation ............................9

Figure 4. Wiring Diagram for 1.5 - 4 Ton

Models (without CoreSense

TM

) .........9

Figure 5. Wiring Diagram for 1.5 - 4 Ton

Models (with CoreSense

TM

) ..............10

Figure 6. Wiring Diagram for 5 Ton Models

(without CoreSense

TM

) ......................11

Figure 7. Wiring Diagram for 5 Ton Models

(with CoreSense

TM

) ...........................12

Table 3. LED Diagnostics for CoreSense

TM

Diagnostics Module ............................13

inStallation / perFormance checKliSt 16
replacement partS .....................................16

Summary of Contents for S4BE-018 Series

Page 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Page 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Page 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Page 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Page 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Page 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Page 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Page 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Page 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Page 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Page 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Page 14: ...14...

Page 15: ...15...

Page 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...