Nortek S4BE-018 Series Installation Instructions Manual Download Page 7

7

air conditioner maintenance

 Warning:

to prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

 caution:

the unit should never be operated without a 

filter in the return air system. replace disposable 

filters with the same type and size.

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed 

at the factory and does not require lubrication.

reFrigerant charging

 Warning:

S4Be Split System air conditioners are shipped 

charged with r410a refrigerant and ready 

for installation. if repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

After refrigerant line connections are completed, it is 

required that you leak check and evacuate the indoor 

section and all line connections (using proper methods) 

before finalizing the full system refrigerant charge.

•  Refrigerant  charging  charts  are  applicable  only  to 

matched equipment and listed airflows for the indoor 

coil. Refer to 

Figure 3, (page 8)

 for correct system 

charging.

•  S4BE outdoor units with non-AHRI listed indoor coils 

are not recommended. Deviations from rated airflows or 

non-listed combinations may require modification to the 

expansion device and refrigerant charging procedures 

for proper and efficient system operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the outdoor 

unit. Use only gage line sets which have a “Schrader” 

depression device present to actuate the valve.

•  A high-pressure switch is factory-installed and located 

in the liquid line internal to the outdoor unit. The switch 

is designed to protect the system when very high 

pressures occur during abnormal conditions. Under 

normal conditions, the switch is closed. If the liquid 

pressure rises above 575 psig, then the switch will open 

and de-energize the outdoor unit. The switch will close 

again once the liquid pressure decreases to 460 psig. 

Please note that the switch interrupts the thermostat 

inputs to the unit. Thus, when the switch opens and 

then closes, there may be a 5 minute short cycling delay 

before the outdoor unit will energize.

•  A low-pressure switch (select models only) is factory-

installed and located in the suction line internal to 

the outdoor unit. The switch is designed to protect 

the compressor from a loss of charge. Under normal 

conditions, the switch is closed. If the suction pressure 

falls below 5 psig, then the switch will open and de-

energize the outdoor unit. The switch will close again 

once the suction pressure increases above 20 psig. 

Please note that the switch interrupts the thermostat 

inputs to the unit. When the switch opens and then 

closes, there will be a 5 minute short cycling delay 

before the outdoor unit will energize.

charging the unit in ac mode

(At outdoor temperatures above 55° F for 
optimized sub-cooling of 10° F - 12° F.)

1. With the system operating at steady-state, measure the 

liquid refrigerant pressure (in psig) at the outdoor unit 
service valve.

2. Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure from 

Figure 3, (page 8)

.

•  If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined 

in Step 3, then there is too much charge in the 

system. Remove refrigerant and repeat Steps 1 

through 3 until the system is correctly charged.

•  If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 

Step 3, there is too little charge in the system. Add 

refrigerant and repeat Steps 1 through 3 until the 

system is correctly charged.

Summary of Contents for S4BE-018 Series

Page 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Page 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Page 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Page 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Page 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Page 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Page 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Page 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Page 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Page 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Page 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Page 14: ...14...

Page 15: ...15...

Page 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...

Reviews: