Nortek S4BE-018 Series Installation Instructions Manual Download Page 13

13

Table 3

table 3. led diagnostics for coreSense

tm

 diagnostics module

alert code

alert condition

locK leVel

locK indication

normal run

Solid Yellow

Normal operation, no trip

N/A

N/A

code1

Yellow Flash 1

Long run time. Compressor is on running for more than 18 hours.
(Code1 is disabled in Heat Pump Mode)

N/A

N/A

code2

Yellow Flash 2

Compressor (pressure) trip. Compressor runs for 12 sec to 15 min 
followed by a compressor trip condition lasting for more than 7 min.

4x consecutive

Red: Flash2

Yellow: Off

code3

Yellow Flash 3

Pressure switch cycling. Compressor runs for 12 sec to 15 min followed 
by a compressor trip lasting between 35 sec to 7 min.

4x consecutive

or 10x total

Red: Flash3

Yellow: Off

code4

Yellow Flash 4

Locked rotor. Compressor trips within a compressor run time of 12 sec 
and does not start within 35 sec.

10x consecutive

Red: Flash4

Yellow: Off

code5

Yellow Flash 5

Compressor (moderate run) trip. Compressor runs for 15 min to 18 hrs 
followed by a compressor trip lasting longer than 7 min.

4x consecutive

or 10x total

Red: Flash5

Yellow: Off

code9

Red Flash 9

The current to the PROT terminal is greater than 2A.

Current >2A

for 40ms

Red: Flash9

Yellow: Off

trip

Solid Red

Demand is present, but compressor is not running.

N/A

N/A

Summary of Contents for S4BE-018 Series

Page 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Page 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Page 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Page 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Page 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Page 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Page 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Page 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Page 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Page 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Page 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Page 14: ...14...

Page 15: ...15...

Page 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...

Reviews: