Nortek S4BE-018 Series Installation Instructions Manual Download Page 16

inStallation / perFormance checKliSt

electrical SyStem

Electrical connections tight?

YES

NO

Line voltage polarity correct?

YES

NO

Rated Voltage: ___________________________________ VOLTS

L1-L2 Volts: _____________________________________ VOLTS

L1-L3 Volts: _____________________________________ VOLTS

L2-L3 Volts: _____________________________________ VOLTS

Avg. Volts: ______________________________________ VOLTS

Max. deviation of voltage
from avg. volts: ___________________________________ VOLTS

% Volt imbalance: ________________________________ VOLTS

Blower Motor HP: ________ Sheave Setting ___________# Turns

Has the thermostat been calibrated?

YES

NO

Is the thermostat level?

YES

NO

Is the heat anticipator setting correct? 

(If Applicable)

YES

NO

709606a

 (Replaces 7096060)

inStallation addreSS:

CITY ________________________ STATE ________________

UNIT MODEL # ________________________________________

UNIT SERIAL # _______________________________________

inStaller name:

CITY _______________________

STATE ________________

Unit Installed Minimum clearances 

shown on 

page 3

?

YES

NO

Has the owner’s information been 

reviewed with the customer?

YES

NO

Has the Literature Package been left 

with the unit?

YES

NO

reFrigeration SyStem

Was unit given 24 hr warm up period 

for crankcase heaters?

YES

NO

Stage-1 Liquid Pressure (high side) ________________________

Stage-1 Suction Pressure (low side) ________________________

propoSition 65 Warning:

Warning: this product contains chemicals known 
to the state of california to cause cancer.

Warning: this product contains chemicals known 
to the state of california to cause birth defects or 
other reproductive harm.

replacement partS

Replacement parts are available through your distributor. 

Please have the complete model and serial number of 

the unit when ordering replacement parts.

electrical:

•  Capacitors

•  Temperature Limit Switches

•  Compressors

•  Thermostats

•  Contactors

•  Time Delay Relays

•  Pressure Switches

•  Transformers

•  Relays

motors:

•  Blower Motor
•  Fan Motor

components:

•  Blower Assembly

•  Fan Grille

•  Cabinet Panels

•  Filter/Driers

•  Expansion Valves

Specifications & illustrations subject to change without notice or incurring obligations (05/15).
O’Fallon, MO, © Nortek Global HVAC LLC 2015. All Rights Reserved.

Summary of Contents for S4BE-018 Series

Page 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Page 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Page 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Page 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Page 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Page 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Page 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Page 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Page 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Page 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Page 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Page 14: ...14...

Page 15: ...15...

Page 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...

Reviews: