Nortek S4BE-018 Series Installation Instructions Manual Download Page 6

6

Start up & adJuStmentS

pre-Start check list

 Verify the indoor unit is level and allows proper 

condensate drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

 Verify air filters are cleaned and properly installed.

 Verify duct work is sealed to prevent air leakage.

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

  Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

 Verify the thermostat is wired correctly.

Start-up procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the system.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan 

mode to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 
balanced air distribution. If insufficient air is detected, 
examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the 

blower stops running.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and 
verify the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 
and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds occur, 
determine the source of the noise and correct as 
necessary.

3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 
Verify the fan and compressor cycle off with the 
thermostat. 

note:

 The blower should also stop unless 

fan mode is set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or 

electric heat) and indoor blower energize. Feel the air 
being circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.

Table 2

table 2. thermostat Wire gauge

thermoStat

Wire gauge

maximum recommended

 thermoStat Wire length (Ft)

24

25

22

45

20

70

18

110

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 
the indoor equipment.

• 

The outdoor unit is designed to operate from a 24 VAC 
Class II control circuit. The control circuit wiring must 
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having 
jurisdiction.

•  The

 low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 

wire gauge and wire lengths for typical thermostat 

connections are listed in 

Table 2

.

•  The

 

thermostat should be mounted about 5 feet above 

the floor on an inside wall. DO NOT install the thermostat 
on an outside wall or any other location where its 
operation may be adversely affected by radiant heat from 
fireplaces, sunlight, or lighting fixtures, and convective 
heat from warm air registers or electrical appliances. 

Refer to the thermostat manufacturer’s instruction sheet 

for detailed mounting and installation information.

Summary of Contents for S4BE-018 Series

Page 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Page 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Page 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Page 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Page 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Page 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Page 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Page 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Page 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Page 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Page 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Page 14: ...14...

Page 15: ...15...

Page 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...

Reviews: