background image

18

Installation Example

Elevation:

 ................................................... 5,000 feet

Type of Gas:

 ............................................Natural Gas

Local Heating Value of Gas:

 ...............................750

Determine which natural gas table to use. From 

Table 

11, (page 26)

, find 750 and follow down the column, 

stop at the 5,000 feet row. The heating value listed is 

LOW. 

Table 13, (page 26)

 will be used to determine 

orifice size and verify manifold pressure.

After the gas piping to the furnace is complete, all 

connections must be tested for gas leaks. This includes all 

fittings, pipe connections at the main gas valve, emergency 

shutoff valve, and flexible gas connectors (if applicable). 

The soap and water solution can be applied on each 

joint or union using a small paintbrush. If any bubbling is 

observed, the connection is not sealed adequately and 

must be retightened. Repeat the tightening and soap 

check process until bubbling ceases.

 CAUTION:

When pressure testing gas supply lines at 

pressures greater than 1/2 psig (14 inch W.C.), the 

gas supply piping system must be disconnected 

from the furnace to prevent damage to the gas 

control valve. If the test pressure is less than or 

equal to 1/2 psig (14 inch W.C.), close the manual 

shut-off valve

Flue Gas Sampling

It may be necessary to take flue gas sampling in order 

to check the performance after furnace installation. A 

flue gas sample may be taken from the heat exchanger, 

which is located behind the hole of the top-front of blower 

compartment.
1. Turn off all electric power to the appliance.

2. Remove the black plastic cap located above the blower. 

Do not discard cap.

3. Drill a hole through the top of the blower compartment. 

NOTE: 

Hole diameter should be same size as sampling 

tube.

4. Insert sampling tube through the drilled hole and into 

the heat exchanger.

5. After a complete check and adjustment of furnace 

performance, seal the drilled hole with a screw larger 

than the hole. 

NOTE:

 Seal the screw threads with silicon 

sealant - rated at least 500° F.

6. Plug the outside hole with the plastic cap removed in 

step 3.

High Altitude Conversion

 WARNING:

The reduction of input rating necessary for high 

altitude installation may only be accomplished 

with factory supplied orifices. Do not attempt to 

drill out orifices in the field. Improperly drilled 

orifices may cause fire, explosion, carbon 

monoxide poisoning, personal injury or death.

High altitude conversion with this furnace depends on 

the installation altitude and the heating value of the gas. 

The installation of this furnace at altitudes above 2,000 

feet must meet the requirements of the National Fuel Gas 

Code or local jurisdiction. In Canada, the requirements for 

high altitude are different and governed by CSA B149.1. 

Always consult your local code authority.

This furnace is shipped from the factory with orifices and 

gas regulator settings for natural gas operation at sea 

level altitudes. At 2,000 feet, the NFGC requires that this 

appliance be derated 4% for each 1000 feet of altitude. For 

example, the input needs to be reduced 8% at 2,000 feet, 

12% at 3,000 feet and etc. This deration is in reference to 

the input rate and gas heating value at sea level.
To derate the furnace requires knowing the heating value of 

the gas at the installation site. Heating values at particular 

job sites vary for two reasons:
1. The chemical mixture of the gas varies from region to 

region and is expressed as the “sea level heating value”.

2. The heating value varies by altitude. For this reason, 

especially in high altitude areas, the local gas utility 

specifies the heating value at the residence’s gas meter 

as the “local value”.

For added flexibility, two tables have been provided for 

natural gas installations with high or low heating values 

at sea level. 

Table 12, (page 26)

 & 

Table 13, (page 26)

 

contain the manifold pressure and orifice sizes to use 

at various altitudes. 

Table 12

 (HIGH) is for natural gas 

installations with a heating value of more than 1,000 Btu 

per cubic foot and 

Table 13

 (LOW) is for less than 1,000 

Btu per cubic foot. To determine which table to use: 
1. Consult the local utility for the local heating value at 

your installation site.

2. From 

Table 11, (page 26)

find your local heating value 

as supplied by the utility company. Follow down the 

column and stop at your altitude level.

3. If your sea level heating value is HIGH, use 

Table 12

 

or if it’s LOW, use 

Table 13

See 

Example

.

After changing the orifices, it is required that you measure 

the gas input rate. This may be accomplished in the usual 

way, by clocking the gas meter and using the local gas 

heating value. See Verifying Input Rate (

page 21

).

IMPORTANT NOTE:

Observe the action of the burners to make sure there 

is no yellowing, lifting or flashback of the flame.

Summary of Contents for MG1 Series

Page 1: ...ier call the fire department QUE FAIRE S IL Y A UNE ODEUR DE GAZ N essayez d allumer aucun appareil Ne touchez aucun interrupteur lectrique n utilisez aucun t l phone dans le b timent vacuez l immeubl...

Page 2: ...nversion to Propane LP Gas 19 Atmospheric Direct Ignition Furnaces 19 Measuring the Supply Gas Pressure 19 Measuring the Manifold Pressure 19 STARTUP ADJUSTMENTS 20 Operating Instructions Direct Ignit...

Page 3: ...pendant l installation l entretien et le fonctionnement de cette fournaise Le non respect des recommandations de s curit peut causer des dommages l quipement ou des blessures graves voire mortelles A...

Page 4: ...ANSI NFPA 70 CANADA Canadian Electrical Code CSA C22 1 Gas Piping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes CANADA NSCNGPIC General Installation US Current edition of the NFGC and...

Page 5: ...sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide min 250 sq in 1613 cm open free area in front or side...

Page 6: ...e a louvered door with a minimum of 250 in2 free area with the openings in the closet door in line with the louvered openings in the furnace door A fully louvered closet door may be used See Circulati...

Page 7: ...ode ANSI C1 NFPA 70 Gaspipingisnotruninorthroughthereturnductsystem CAUTION HAZARDOFASPHYXIATION Negativepressure inside the closet with closet door closed and the furnace blower operating on high spe...

Page 8: ...1 7 8 2 7 8 C L Figure 7 Cut Out Dimensions for Round Duct Connectors Bend tabs up 90 Mounting Plate Duct Connector Connector Tabs Supply Air Duct Hole for Gas Line Wood Floor Figure 8 Standard Duct...

Page 9: ...to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 8 For round ducts see Figure 7 page 8 1 Measure 10 from the rear wall or alcove and mark the centerline...

Page 10: ...ector and the mounting plate to the wood floor with appropriate size screws 5 Connect the round supply duct to the underside of the duct connector and secure them with field supplied sheet metal screw...

Page 11: ...ING F S AW1523 0 2 4 A S 15 23 F S AW2135 0 2 4 A S 21 35 F S AW2747 0 2 4 A S 27 47 F S AW3563 0 2 4 A S 35 63 F S AW5195 0 2 4 A S 51 95 NOTE Not all models are available Check with your local distr...

Page 12: ...ough the opening cut on the roof 3 Connect inner flue pipe to vent collar of the furnace See Figure 22 4 Connectcombustionairpipetofurnacecollarwithsheet metal screw See Figure 22 NOTES Itisrecommende...

Page 13: ...stallations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes It is recommended that 115VAC line voltage be supplied to the f...

Page 14: ...unless the polarity and ground are properly connected as shown in Figure 25 and Figure 26 page 14 ForinstallationofA sizeCabinetfurnaces allowsufficient slack in the wiring if an optional cooling coi...

Page 15: ...Specifications Thermostat Wire Gauge FURNACE MODEL NUMBER FURNACE INPUT BTUH CABINET WIDTH IN NOMINAL ELECTRICAL SUPPLY MINIMUM OPERATING VOLTAGE MAXIMUM OPERATING VOLTAGE MAXIMUM FURNACE AMPERES MAXI...

Page 16: ...follow all safety warnings could result in serious injury death or property damage This furnace may be installed with left right or bottom gas entry Whenconnectingthegassupply provideclearance between...

Page 17: ...60HZ 30 vac Normal Anticipator Setting 0 4 Manifold Pressure for Natural Gas 3 5 w c Manifold Pressure for LP Gas 10 w c AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissement...

Page 18: ...e explosion carbon monoxide poisoning personal injury or death High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas The installation of this...

Page 19: ...Pressure To obtain an accurate pressure reading turn off all gas appliances i e Dryers water heaters stoves etc at their ON OFF control or individual gas valves 1 Remove the inlet pressure plug from t...

Page 20: ...ace in service it must be checkedtoensureitisequippedforthetypeofgas being used The burner flame must be observed andadjustedifnecessary Failuretoobservethis cautionmayresultinunsafeoperation explosio...

Page 21: ...supplier See page 19 Verifying Adjusting Temperature Rise Confirm the temperature rise through the furnace is within the limits specified on the furnace rating plate Any temperature rise outside the...

Page 22: ...to the furnace before shutting off the electrical supply 7 When call for heat is satisfied the thermostat contacts open thegasvalveshutsoffgasflowandthecombustion blower remains on for a 30 45 second...

Page 23: ...gnitortipforflamerectification Misalignedignitordoesnotallowflametocontactignitor tip for flame rectification Burner Short Cycling Thermostat Calls for Heat Limit Switches Closed Check for polarity Ch...

Page 24: ...h Inspect the combustion chamber blower compartment flue collar and Roof Jack Check the gas valve if applicable and fuel line connections for leaks Make any adjustments necessary for good operation WA...

Page 25: ...439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 16...

Page 26: ...27 24 Service Orifice Size Table 13 High Altitude Deration Chart for Natural Gas Low Heating Value Table 11 Natural Gas Heating Values LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE ABOVE SEA LEVEL BTU...

Page 27: ...115V N C L R GROUND SCREW GROUND SCREW GAS VALVE NEUTRAL L1 WIRE NUTS SUPPLIED BY INSTALLER 1 2 3 4 5 N L C G ECM BLOWER MOTOR G W Y R C CONTROL LIGHTS 1 2 1 2 BLACK BLACK 1 2 3 4 5 6 1 2 3 4 5 6 MOTO...

Page 28: ...Gas valve De energized when it should be Energized Rapid Flash Reverse Polarity Continuous On Normal Operation Flash codes stored in memory auto erased after 14 days Flash codes NOT stored in memory...

Page 29: ...79 53 2 Med Low 996 57 960 59 924 62 885 64 848 67 1 Low MG1E 090F1AAM1 MODEL NAME HEATING INPUT MOTOR SPEED EXTERNAL STATIC PRESSURE IN W C 0 1 0 2 0 3 0 4 0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM...

Page 30: ...6 0 7 0 8 CFM CFM CFM CFM CFM CFM CFM CFM MG1E 077F1AAM1 77 000 BTU Hr 5 High 1 573 1 541 1 511 1 479 1 452 1 419 1 388 1 358 4 Alternate 1 333 1 300 1 268 1 236 1 201 1 162 1 129 1 093 3 Med High 1 2...

Page 31: ...31...

Page 32: ...Literature Package been left with the unit YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict...

Reviews: