background image

4

 

NOTE:

 The holes in the drain pan extension should be 

pressed over the nibs molded into the drain pan. Which 

pair of holes to use will depend on whether the unit is 

installed horizontal left or horizontal right. Verify proper 

positioning for clearance thru the top of the coil cabinet 

before affixing. The drain pan extension can be installed 

and removed after the ductwork has been attached to the 
cased coil.

7. Connect the refrigerant lines as outlined in the Refrigerant 

Lines Connection section.

8. Seal the enclosure as required to minimize air leakage.

9. Reinstall the coil access door.

10. Restore electrical power to the furnace.

Horizontal Right Installations

1. Disconnect all electrical power to the furnace.

2. Remove the coil access door.

3. Remove the plug and knockout from one of the threaded 

holes in the horizontal drain pan.

 CAUTION:

The knockout must be removed and discarded 

to ensure proper condensate drainage. Failure to 

do so may result in structural damage, premature 

equipment failure, or possible personal injury.

4. Place the horizontal drain pan on the opposite side of the 

coil. 

NOTE:

 If unit has 2 sets of knockouts, remove the 

other set of knockouts in the coil spacing plates and insert 

support rod.

5. Install plug (from horizontal drain pan) in the open drain 

hole in the drain pan at the bottom of the unit. This will 

block bypass air from entering the system.

6. Slide the coil and the horizontal drain pan assembly back 

into the unit.

7. Remove the drain line knockout from the coil access door. 

This will allow access to the horizontal drain.

8. Install drain pan extension (if supplied with unit).
 

NOTE:

 The holes in the drain pan extension should be 

pressed over the nibs molded into the drain pan. Which 

pair of holes to use will depend on whether the unit is 

installed horizontal left or horizontal right. Verify proper 

positioning for clearance thru the top of the coil cabinet 

before affixing. The drain pan extension can be installed 

and removed after the ductwork has been attached to the 
cased coil.

9. Connect the refrigerant lines as outlined in the Refrigerant 

Lines Connection section.

10. Seal the enclosure as required to minimize air leakage.

11. Reinstall the coil access door.

12. Restore electrical power to the furnace.

Downflow Installations

C7 coils may be installed in downflow applications. It is 

required that the furnace and coil cabinets are securely 

mounted together before setting in place. Fossil fuel 

applications require the coil to be placed in the supply air 

stream only.

REFRIGERANT LINE CONNECTIONS

IMPORTANT NOTE TO INSTALLER

C7 Coils are not factory charged with refrigerant. It will 

be necessary to evacuate the indoor coil and lineset 

prior to charging. Refer to the outdoor unit installation 

manual for detailed charging instructions.

System Depressurization

1. Remove the cap (

Figure 1

) from the end of the liquid line.

2. Verify pressurization by depressing the Schrader valve 

on the end of the liquid line. Listen for any escaping gas. 

If there is no pressure, test the coil for leakage.

•  If leakage is found, clearly mark the location of the leak 

and return the coil to the distributor for processing.

•  If no leaks are found, the coil may be installed.

3. Depress the valve to relieve all pressure from the coil.

4. Remove and discard the valve core and valve core holder 

on the liquid line.

5. Remove the rubber plug from the suction line.

Installing the TXV

(For Optional Bulkhead Mounted TXV’s)

1. Install the TXV retaining nut onto the inlet end of the TXV. 

See 

Figure 6 (page 8)

.

2. Add small amount of HVAC approved thread lock to the 

inlet end of the TXV.

3. Install the liquid line and accessory retaining nut onto the 

end of the TXV. For liquid line kit numbers, see 

Table 2, 

(page 5)

.

 CAUTION:

To prevent damage to the unit or internal 

components, it is recommended that two wrenches 

be used when loosening or tightening nuts. Do not 

over tighten!

4. Align the retaining nut on the TXV body and hand tighten 

both components. Mark a line on both bodies and then 

tighten an additional ¼ turn using two wrenches. See 

Figure 

2 (page 5)

NOTE:

 The movement of the two lines will 

show how much the nut is tightened. If a torque wrench 

is used, tighten to 10-12 ft lbs or 14-16 Nm.

Orifice Removal & Installation

NOTE:

 Before proceeding, perform steps 1 - 3 in the System 

Depressurization section and confirm that the restrictor 

orifice size meets the requirements outlined in the outdoor 

unit installation manual. Factory supplied orifice sizes are 

listed in 

Table 3

Table 4

, or 

Table 5, (page 7)

. If the orifice 

must be replaced, follow steps 1 - 5.

Suction 

Line

Liquid 

Line

Cap

Schrader 

Valve

Figure 1. Suction & Liquid Line Locations

Summary of Contents for C7BA

Page 1: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 2: ...unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not posses mechanical skills ortools callyourlocaldealerforassistance Under no circu...

Page 3: ...70A 3 920671A 3 5 920672A 4 920673A 5 Table 1 TXV Kit Part Numbers COIL INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failuretofollowsafetywarningsexactlycouldresult in serious injury...

Page 4: ...re electrical power to the furnace Downflow Installations C7 coils may be installed in downflow applications It is required that the furnace and coil cabinets are securely mounted together before sett...

Page 5: ...s NOTE If installing a TXV please follow the instructions supplied with the kit See Table 2 for kit part numbers 1 Remove the grommet from the suction line making note of its orientation and fit 2 Rem...

Page 6: ...stem checkout inspect the drain line and connections to verify proper condensate drainage Air Filter Air filters are not supplied as an integral part of this coil however anairfilterkitisavailable Ref...

Page 7: ...in 14 1 2 14 1 2 17 1 2 17 1 2 17 1 2 21 21 21 21 24 1 2 24 1 2 24 1 2 H Height in 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 30 1 4 30 1 4 30 1 4 30 1 4 30 1 4 HL Height of Liquid Line in 23 1...

Page 8: ...Coil Dimensions W HS HL H 5 8 4 17 3 4 20 3 4 FRONT VIEW TOP VIEW Distributor Thermal Expansion Valve TXV Door TXV Retaining Nut Liquid Line Stub w Screen Accessory Retaining Nut Grommet Figure 6 TXV...

Page 9: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 10: ...ant son installation son entretien et son utilisation Les personnes non qualifi es ne doivent pas tenter d interpr ter ces instructions ou d installer cet quipement Si vous ne poss dez pas les comp te...

Page 11: ...s blessures graves ou des dommages mat riels importants Un entretien inappropri peut provoquer un fonctionnement dangereux des blessures graves la mort ou des dommages mat riels Avant toute interventi...

Page 12: ...e que les armoires du la fournaise et les bo tiers de serpentins doivent tre solidement fix s ensemble avant l installation du serpentin Les applications au combustible fossile requi rent que le serpe...

Page 13: ...Tableau 2 pour les num ros de pi ces des trousses 1 Retirez le passe fils de la conduite de succion en notant son orientation et son ajustement 2 Retirez la porte d acc s au serpentin 3 Enlevez le bou...

Page 14: ...ssurerl vacuationappropri e du condensat Filtre air Les filtres air ne sont pas fournis avec ce serpentin toutefois une une trousse de filtre air est disponible Consultez la Liste des pi ces de rechan...

Page 15: ...26 75 26 75 26 75 26 75 30 25 30 25 30 25 HL Hauteur de la conduite de liquide po 17 5 17 5 17 5 17 5 17 5 17 5 23 5 23 5 23 5 23 5 27 27 27 HS Hauteur de la conduite de succion po 15 5 15 5 15 5 15...

Page 16: ...bligations 10 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved Figure 5 Dimensions du serpentin W HS HL H 5 8 4 17 3 4 20 3 4 VUE D AVANT VUE DE DESSUS Distributeur D tendeur thermostati...

Reviews: